Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power Requirements

This section provides information regarding array module AC power requirements, power cord routing instructions, and site wiring conditions.

The AC power source must provide the correct voltage, current, and frequency specified on the manufacturer’s nameplate. Internal AC power units for rackmount cabinets must be able to handle the power specifications for these units. Refer to Table 4-6and Table 4-7for more information.

 

 

Table 4-6

E2400 10x Array Module Power Requirements

 

 

 

 

 

 

 

Item

 

Unit of Measure

Requirement

 

 

 

 

 

 

Circuit Breaker

Slow-blow Fuse

10 A per Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Range

 

High Range

 

 

 

 

 

 

 

 

 

Nominal Voltage

90 to 136 VAC

 

198 to 264 VAC

 

 

 

 

 

 

 

 

 

 

Frequency

 

50 to 60 Hz

 

50 to 60 Hz

 

 

 

 

 

 

 

 

AC Power

Idle Current

 

3.39 A

 

1.45 A1

 

 

Maximum Operating Current

3.53 A

 

1.50 A1

 

 

Maximum Surge Current

5.19 A

 

2.10 A1

 

 

(10-drive spin up)

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Typical current at 240 VAC, 60 Hz at 0.70 power efficiency, 0.99 power factor.

 

 

 

Table 4-7

E2400 14x Array Module Power Requirements

 

 

 

 

 

 

Item

 

Unit of Measure

Requirement

 

 

 

 

Circuit Breaker

 

Slow-blow Fuse

10 A per Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Range

 

High Range

 

 

 

 

 

 

 

 

 

 

Nominal Voltage

90 to 136 VAC

 

198 to 264 VAC

 

 

 

 

 

 

 

 

 

 

Frequency

50 to 60 Hz

 

50 to 60 Hz

 

 

 

 

 

 

AC Power

 

Idle Current

2.9 A1

 

1.3 A2

 

 

 

 

 

 

 

 

 

 

Maximum Operating

3.3 A1

 

1.4 A2

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Surge Current

5.9 A1

 

2.4 A2

 

 

 

(14-drive spin up)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1Typical voltage: 100 V AC, 60 Hz at 79% power supply efficiency and 0.99 power factor.