. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements

Environmental Requirements

The drive module is designed to operate in the environment defined in Table 3-5and Table 3-6 on page 3-7.

Table 3-5 Drive Module Environmental Requirements

Condition

Parameter

Requirement

 

FC-1 10x, FC-1 14x, and FC-2 14x

 

 

 

 

 

 

 

 

 

Operating Range

10° C to 40° C (50° F to 104° F)

 

 

Maximum Rate of Change

10° C (18° F) per hour

Temperature

 

Storage Range

-10°C to 50° C (14° F to 122° F)

 

Maximum Rate of Change

15° C (27° F) per hour

 

 

 

 

Transit Range

-40°C to 60° C (-40°F to 140° F)

 

 

Maximum Rate of Change

20° C (36° F) per hour

 

 

Operating Range

20% to 80%

 

 

 

 

 

 

Storage Range

10% to 90%

Relative Humidity

 

 

 

 

Transit Range

5% to 95%

No condensation

 

 

 

 

 

 

Maximum Dew Point

26° C (79° F)

 

 

Maximum Gradient

10% per hour

 

 

 

 

Sound

 

Sound Power

6.0 bels

 

 

 

 

Sound Pressure

60 dBA

 

 

 

 

 

Altitude

Operating and Storage

3000 m (9840 ft.)

(Above Sea Level)1

 

 

 

 

Transit

12,000 m (40,000 ft.)

 

 

 

Altitude

Operating, Storage, and Transit

30.5 m (100 ft.)

(Below Sea Level)

 

 

 

 

 

 

1 If you plan to operate a drive module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level, lower the environmental temperature 1.7° C (3.3° F) for every 1000 m (3280 ft.) above sea level.

Table 3-6 Drive Module Heat Dissipation

Model

Low Profile (LP)

Half Height (HH)

18 GB and 36 GB Drives

36 GB and 73 GB Drives

 

 

 

 

FC-1 10x

1036 Btu/hr (0.306 kVA or 303 W)

1070 Btu/hr (0.33 kVA or 313 W)

 

 

 

FC-1 14x

1050 Btu/hr (0.309 kVA or 306 W)

Not applicable.

 

 

 

FC-2 14x

1084 Btu/hr (0.320 kVA or 317 W)

Not applicable.

 

 

 