5. Installing the Chimney System
Start by attaching the first chimney section to the collar on top of the fireplace.
Install the pipe as pictured in Figure 14. When you get a good lock, you will hear the pipe clearly snap to- gether. Once sections are
When installing elbows, only outer pipe will snap- lock. Middle pipes simply slide into position. Be sure to always attach straps on upper elbow to a structural framing member. (Fig. 15)
Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.
Installing the Firestop Spacer
in the Ceiling Hole
A firestop spacer is used to keep pipe spaced properly and required for safety.
Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. Note: A firestop spacer is not required at the roof.
Hole sizes listed in Figure 10 for angled firestop spac- ers provide minimum required air space to chimney pipe for ceiling thickness up to eight (8) inches. When combined thickness of ceiling material, ceiling joists and flooring material exceeds eight (8) inches, adjust- ments must be made in framing to assure that minimum air spaces to chimney are maintained.
Proper Firestop Spacer Installation
Figure 16 shows different installation procedures for both an area that is an attic and an area that is not an attic.
ODSHR Series
Pipe Section
Pipe
Rim
Hem
Lance
Pipe
Rim
FP558SHR
Fig. 14 Install pipe, listening for the snap-lock to fasten.
Support Structure
Elbow Strap (must be tight)
Ceiling
Elbow StrapHole
Framing
Angle Firestop
Chimney Support
Angled StrapStrap
(must be tight)
FP270/271
Fig. 15 Attach straps to a structural framing member.
If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole.
If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.
20002264
| Attic Installation | Ceiling Installation |
|
| Nails (4) |
|
|
| Firestop Spacer | Joist |
|
| Joist | Firestop |
|
|
| Spacer |
|
| Flange Down Into Hole | Nails (4) |
|
|
|
| |
|
| Flange Up Into Hole | FP285 |
Fig. 16 | Installing firestop spacer. |
|
|
|
|