o Grounding the generator
- If such grounding conductor or grounding electrode is unavailable, connect the grounding lug of the generator to the grounding terminal of the using
|
| electric tool or appliance. |
|
| CAUTION |
|
| Generator must be grounded when the electrical |
|
| appliance is grounded. |
|
| Failure to ground generator may lead to electric |
|
| shock. |
I | I | DC application (For charging 12V battery only) |
|
| 0 DC receptacle is used only for charging a 12V |
|
| battery. |
|
| 0 Connection of battery charging cables : |
|
| Using the attached DC plug, connect its positive and |
|
| negative terminals to the corresponding battery |
|
| terminals. |
I | DC receptacle I |
|
0Battery charging procedures :
-Make the proper connection as mentioned above, be careful not to make a wrong connection. Be sure to disconnect all cables connected from battery to any other appliance.
-Remove all plugs from top of battery.
-Check electrolyte level and add distilled water if necessary, to bring the electrolyte level to the level marked "UPPER".
-Start engine to charge battery.
The charging time varies depending on the condition of
discharge. The specific gravity of a battery electrolyte indicates the state of charge in each battery cell. While charging battery, check the specific gravity with a hydrometer, using a thermometer to correct hydrometer reading for temperature. A corrected specific gravity reading of 1.26 to 1.28 in all cells indicates a fully charged battery.
Example : In case of