FAULT FINDING

Continued from page

52 of fault finding

no

With the boiler and heating circuit warm does the burner pressure reduce if the heating temperature setting is reduced to minimum?

yes

no

When a DHW tap is

opened and the DHW temperature is set to maximum, does the water become hot?

Is there between 0V dc

and 16V dc at the connections on the modulating coil? (0=min, 16=max)

yes

Is the burner pressure within min and max value* with the boiler running?

yes

Repair faulty gas

valve

Is the boiler mode

setting correct?

(Refer to frame 62)

yes

no

no

Adjust burner pressure. Refer to frame 35.

no

Follow the instruction “Boiler mode setting” (Refer to frame 62)

Is the continuity of the

modulator harness

O.K?

yes

Repair faulty PCB

no

Repair or replace

faulty wiring

FAULT FINDING

yes

Is the red LED

illuminated on DHW

flow sensor?

yes

no

Is there 230V

ac between

Blue and

Black at the

3---way valve connection?

yes

Remove the

 

motor

 

assembly, with

 

230V at the

 

connections is

 

the spindle fully

no

retracted? Refer

 

to frame 76.

 

yes

Replace

faulty valve

body

assembly

no

Is the

continuity of

the 3---way

valve harness O.K?

yes

Repair faulty

PCB

Replace

faulty motor

assembly

no

Is there 5V dc between

Red and Blue on

connecting harness?

yes

no

Repair or

replace

faulty

wiring

no

Replace the

sensor. Is

red LED

illuminated?

yes

Faulty sensor now replaced

no

Is the harness continuity O.K?

yes

Repair faulty PCB

no

Dismantle the DHW detector valve and clean. Refer to frame 66.

Reassemble.

Does the DHW water become hot?

yes

Repair or

replace

faulty wiring

Repair or

replace

faulty DHW

detector

valve

Continued on page 58 of fault finding

* see Table 2 at page 4 for the correct value