GAS APPLIANCE INSTALLATION

7.Pack the insulation removed in step 4 around the pipe to prevent air flowing through the tube either into or out of the firebox.

8.Be sure the gas is turned off at the appliance, then turn the gas on at the cut off valve and test the gas line connections for leaks with soapy water solution or a liquid leak detector. DO NOT USE A MATCH OR OTHER FLAME SOURCE TO CHECK FOR GAS LEAKS. If a gas leak is detected, turn the gas off immediately and fix the leak.

9.Proceed with testing the appliance for leaks and adjusting it as required by the manufacturer instructions.

FIGURE 25

GAS LINE PLUMBING DETAIL

OUTER FIREPLACE WRAP INNER FIREPLACE WRAP

SIDE BRICK

BACK REFRACTORY

SIDE REFRACTORY

BRICK

26" MAX.

FIREPLACE FIREBOX

HEARTH BRICK

GAS LINE ACCESS TUBE

MAINTAIN 1/2" MINIMUM

BRICK

 

AIR SPACE CLEARANCE

 

TO COMBUSTIBLES FOR

 

GAS LINE OUT TO 4" FROM

 

SIDE OF THE FIREPLACE.

 

COMBUSTIBLE MATERIALS

 

MAY BE LOCATED AT ZERO

 

CLEARANCE TO GAS LINE

KNOCKOUT

BEYOND 4" FROM FIREPLACE SIDE.

 

REPACK INSULATION AROUND

CAUTION: WHEN USING A GAS

GAS LINE WHERE IT PASSES THRU GAS

APPLIANCE, THE FIREPLACE DAMPER

LINE ACCESS TUBE FOR

MUST BE SET IN FULLY OPEN POSITION.

PROPER SEAL.

APPLYING DECORATIVE TRIM TO THE FIREPLACE

Do not allow the trim materials to extend closer than 3/8 inch to the vertical edges of the firebox opening if you plan to equip the fireplace with glass doors.

The face of your fireplace may be left exposed or trimmed with any noncombustible material such as brick, stone or marble. If a trim is installed, be sure it is fastened snugly to the face of the fireplace. A crack between the material and the face of the fireplace could pose a fire hazard and impair the proper operation of the fireplace. Blocking the fireplace with framing and attaching the base to the supporting floor will further reduce the possibility of such a crack developing.

Wall ties should be fastened to the face of the fireplace with sheet metal screws and placed in the mortar joints of masonry trim.

Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the fireplace face. Seal the face of the fireplace to the surrounding wall with non-combustible caulk or trim materials to prevent cold air leakage around the fireplace.

The trim should not block or restrict in any way the flow of air into the side air inlets in the face of the fireplace.

Be sure to provide the required floor protection as described in a preceding section of this manual.

Combustible mantles and trim must be installed in accordance with the National Fire Protection Association - ANSI NFPA 211 Standard - Section 7-2.3.3.

25

53D9028. Rev 1 03/03

Page 26
Image 26
Martin Fireplaces SB5400SS manual Applying Decorative Trim to the Fireplace