Operating Instructions for | 1598003200 |
|
|
10.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing the UP key.
10.2 ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty), “P2” ; they automatically stop 10s after the probe restarts normal operation. Check connections before replacing the probe.
T° alarms “HA” and “LA” automatically stop as soon as the thermostat T° returns to normal values or when the defrost starts.
Door switch alarm “dA” stops as soon as the door is closed.
External alarms “EAL”, “BAL” stops as soon as the external digital input is disabled.
11. TECHNICAL DATA
Housing: self extinguishing ABS
Case: face 100x64 mm; depth 45.5mm
Mounting:
Frontal protection: IP65
Connections: ¼” fastons for power, 18” fastons for probes and Digital Inputs
Power supply: 120Vac ± 10%, optional 230Vac ± 10%
Power absorption: 4VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 1 NTC probe
Digital inputs: 2 free voltages
Relay outputs: Dry Contacts
Light: relay SPST 16A, 120Vac;
Alarm: relay SPST 8A, 120Vac
Other output: alarm buzzer
Data storing: on the
Measuring and regulation range:
NTC probe:
Resolution: 1 °F
Accuracy : ±1 °F
12. CONNECTIONS
Back up | D.I.1 |
| D.I.2 |
(9VDC) |
| ||
1 | 2 | 3 | 4 |
8A |
|
|
|
250V | 16A 250V |
|
11 12 13 14
Alarm C. Light C.
| Room |
7 | 8 |
| Hot Key |
18 19
NL
Supply 120V~
Power supply: 230Vac ± 10% models, use the same terminals of the 120Vac version.
5