Step 7. CONNECTING GAS LINE

Make gas line connections. All codes require a shut-off valve mounted in the supply line. Figure

19illustrates two methods for connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.

These appliances are equipped with a gas flex line for use (where permitted) in connecting the unit to the gas line. A gas flex line is provided to aid in attaching the B-Vent appliance to the gas supply. The gas flex line can only be used where local codes permit. See Figure 19 for flex line description. The flex line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex line.

The gas control valve is located in the lower control compartment. To access the valve open the lower control compartment door (see Figure 20). The millivolt control valve has a 3/8" (10 mm) NPT thread inlet port. The electronic control valve has a 1/2" (13 mm) NPT thread inlet port and is fitted with a1/2" x 3/8" (13 mm x 10 mm) NPT fitting.

Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applications).

 

Gas Flex Line Connector

 

Gas

³₈" NPT x ³₈

¹₂" x ³₈" Flare

Valve

Flare Fitting

Shut-Off Valve

 

³₈" Flex Tubing

 

 

 

 

 

Gas

 

 

¹₂ x ³₈ "

Stub

 

 

 

³₈" Nipple

 

Reducer

 

 

 

 

³₈" Union

 

 

 

³₈" Close Nipple

³₈" Shut-Off Valve

Figure 19 - GAS CONNECTION

Open the lower panel or louver assembly by pushing in the right side of the panel or louver assembly and then lowering it forward and down.

Control

Valve

Lower Control

Compartment

Door

OPENING CONTROL

Figure 20

COMPARTMENT DOOR

 

Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open flame to check for leaks.

10

A. Mix a 50% dish soap, 50% water solution. B. Light the appliance (refer to the lighting instructions provided in the Homeowner's

Care and Operation Instructions).

C. Brush all joints and connections with the soapy water solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the “OFF” posi- tion. Either tighten or refasten the leaking connection and retest as described above.

D.When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.

Step 8. OUTSIDE AIR KITS Optional outside make-up air kits, Model FOAK-4 or FAOK-4LD, may be used with these appliances. Refer to the installation instructions packaged with the air kits for specific installation informa- tion. If used, the outside air kit must be installed before the fireplace is framed and enclosed in the finished wall.

Outside air drawn into the fireplace supplies air to the fire for combustion. Only one outside air duct is necessary, if installed. See Figure 1 on Page 2 and Figure 4 on Page 5 for the location of the unit's outside air inlet.

If additional length of duct is necessary, purchase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in any direction.

Note: When installing the air duct vertically, DO NOT terminate the duct closer than 3' below the chimney top.

Outside combustion air ducting may be run upwards or vertically through framing and ceiling joists, with the hood installed through an outside wall and 3' (1 m) below the termination. Ducting may also be run downward through floor joists and under the home to a ventilated crawlspace not considered part of the living area of the home.

Note: Do not terminate outside air kit in attic space under any circumstances.

CAUTION

Never locate inlet where it can be blocked by shrubs, snow drifts, etc. Never locate inlet in garage or any area where there is another fuel burning appliance or products emitting combustible gases such as paint, gasoline, etc. In cold climates, it is recommended the outside air duct be insulated.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

After completing the installation of the optional outside air vent system the outside air control lever must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly rework. Before the operation of the vent system can be tested, the lever securing screw must be removed. See Figure 21.

The hand operated outside air control lever is located on the left side of the fireplace opening.

See Figure 21.

To open the outside air shutter, open the bottom control access panel, reach into the control compartment, and pull the outside air control lever all the way out. The outside air shutter should be fully open when the fireplace is in use and completely closed when the fireplace is not beingused. Closingitwhennotinusewillprevent outside cold air from entering the dwelling.

Outside Air Control Lever

Outside Air Control Lever

Securing screwAir Shutter in Closed Position

Outside Air Control Lever

Outside Air Control Lever

Securing Screw RemovedAir Shutter in Open Position

Outside Air Control Lever

and Securing Screw Locationon Left Side of Cabinet in Lower ControlCompartment Area

Figure 21

Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.