Comet 40-150kVA
1.3.4Mechanical Specifications (UPS Cabinet Only)
Height | 66.70 in/1694 mm |
Width | 32.75 in/832 mm |
Depth | 33.42 in/823 mm |
Weight at 480 VAC in and 480 VAC out |
| |
40/50kVA | 65/80kVA | |
880 lbs/400 kg | 970 lbs/440 kg | 1460 lbs/662 kg |
1.3.5Environmental Specifications
Temperature |
|
Operating: | 0° C to 30° C (32° F to 86° F) continuous |
| 15°C(60°F) to <25° C (<77° F) recommended |
| 40° C (104° F) up to 8 hrs at 75% load |
| |
and storage: | |
Humidity | 0 to 95% |
Altitude | <3000 ft. (1000m), up to 6000 ft. (<2000 m) @ 28° C (82°F) maximum |
1.3.6DB15 Connector Pinouts and Designations
The UPS Manager connector enables communication with the most common computer systems (AS/400, NOVELL, etc.), or with the optional "UPS Manager UM1" software.
Table
UPS Manager Dry Contact Interface (DB15) | Softunor (DB9) |
|
|
Operation on Inverter | Diagnostics (for MGE Customer Care Center use only) |
|
|
Operation on Bypass |
|
|
|
Operation on Battery |
|
|
|
Low Battery Shutdown Warning |
|
|
|
UPS Remote Inverter Shutdown |
|
|
|
Figure 1-9: Pinouts on the DB15 Connector.
DB15
PIJO PC board
|
| NO |
|
| NC |
Breaking |
| NO |
| ||
| ||
| NC | |
capacity of |
|
|
|
| |
contacts is: |
|
|
|
| |
P = 3va |
| NO |
V = 30VDC max. |
| NC |
I = 100mA max. |
| NO |
| ||
|
| |
|
| NC |
|
|
|
|
|
|
5
8Operation on Inverter
Operation on
6Bypass
10
9Operation on Battery
11
13
7Low Battery Shutdown Warning
12
14UPS Remote Inverter Shutdown (3 to 15 VDC voltage signal)
8 7 6 5 4 3 2 1
15 14 13 12 11 10 9
4
GROUND
1
Please note that once the UPS remote inverter shutdown signal is applied, the Inverter stops and the load transfers to bypass after a predetermined time (typically 2 minutes).