Comet 40-150kVA

1.3.4Mechanical Specifications (UPS Cabinet Only)

Height

66.70 in/1694 mm

Width

32.75 in/832 mm

Depth

33.42 in/823 mm

Weight at 480 VAC in and 480 VAC out

 

40/50kVA

65/80kVA

100-150kVA

880 lbs/400 kg

970 lbs/440 kg

1460 lbs/662 kg

1.3.5Environmental Specifications

Temperature

 

Operating:

0° C to 30° C (32° F to 86° F) continuous

 

15°C(60°F) to <25° C (<77° F) recommended

 

40° C (104° F) up to 8 hrs at 75% load

Non-operating

 

and storage:

-30° C to 70° C (-22° F to 158° F)

Humidity

0 to 95% non-condensing

Altitude

<3000 ft. (1000m), up to 6000 ft. (<2000 m) @ 28° C (82°F) maximum

1.3.6DB15 Connector Pinouts and Designations

The UPS Manager connector enables communication with the most common computer systems (AS/400, NOVELL, etc.), or with the optional "UPS Manager UM1" software.

Table 1-2: UPS Manager Dry Contact Interface.

UPS Manager Dry Contact Interface (DB15)

Softunor (DB9)

 

 

Operation on Inverter

Diagnostics (for MGE Customer Care Center use only)

 

 

Operation on Bypass

 

 

 

Operation on Battery

 

 

 

Low Battery Shutdown Warning

 

 

 

UPS Remote Inverter Shutdown

 

 

 

Figure 1-9: Pinouts on the DB15 Connector.

DB15 -pin connector

PIJO PC board

 

 

NO

 

 

NC

Breaking

 

NO

 

 

 

NC

capacity of

 

 

 

 

contacts is:

 

 

 

 

P = 3va

 

NO

V = 30VDC max.

 

NC

I = 100mA max.

 

NO

 

 

 

 

 

NC

 

 

 

 

 

 

5

8Operation on Inverter

Operation on

6Bypass

10

9Operation on Battery

11

13

7Low Battery Shutdown Warning

12

14UPS Remote Inverter Shutdown (3 to 15 VDC voltage signal)

8 7 6 5 4 3 2 1

15 14 13 12 11 10 9

4

GROUND

1

Please note that once the UPS remote inverter shutdown signal is applied, the Inverter stops and the load transfers to bypass after a predetermined time (typically 2 minutes).

1 — 10

System Description and Specifications

86-160310-00 E00

Page 22
Image 22
MGE UPS Systems 40-150kVA user manual Environmental Specifications Temperature, Humidity, Altitude