Installation and User Manual

NOTES:

1.Total width, weight, and heat loss are for system line-up excluding battery cabinets.

2.Data does not include battery data; refer to the installation drawings supplied with your equipment. Consult the installation drawings provided with your equipment.

1.3.1AC Input Ratings

Voltage

 

480 VAC, + 12%, -15%

 

 

 

 

Frequency

 

60 Hz ± 4%

 

 

 

 

Phases

 

3 Ø (phase sequence must be A, B, C, clockwise)

 

 

Wires

 

3 wires plus ground (480-480 VAC only)

 

 

 

Power factor

Approximately 0.98 at full load

 

 

 

Current (on UPS/ on BYPASS) @ 480 VAC

 

 

 

 

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

43A/48A

54A/60A

70A/78A

86A/96A

109A/120A

134A/150A

160A/180A

1.3.2AC Output Ratings

Voltage (inverter only)

480 ± 1% VAC (steady-state conditions)

 

 

 

 

480 ± 5% VAC (transient conditions from 0% to 100% or 100% to 0%)

Frequency

 

60 Hz ± 0.1% (free-running)

 

 

 

Phases

 

3 Ø (phase sequence must be A, B, C, clockwise)

 

Wires

 

3 wires plus ground (480-480 VAC only)

 

 

Power factor

0.8

 

 

 

 

Current @ 480 VAC

 

 

 

 

 

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

48A

60A

78A

96A

120A

150A

180A

Total harmonic

 

 

 

 

 

distortion (THD)

<2% (linear load)

 

 

 

 

 

<3% (for 100% non-linear load with a crest factor of less than 3.0)

Dynamic regulation

± 1% for balanced load

 

 

 

 

 

± 2.5% for 100% unbalanced load

 

 

Dynamic response

± 5% for 100% step load change

 

 

Overload

 

105% - 110% of rated current for 10 minutes

 

 

 

 

>110% - 130% of rated current for 1 minute

 

 

 

 

>130% - 150% of rated current for 10 seconds

 

 

 

>150% of rated current for 0.15 seconds

 

 

1.3.3DC Ratings

Battery voltage (25° C)

float:

 

490 Vdc

 

 

 

 

nominal:

432 Vdc

 

 

 

 

minimum:

360 Vdc

 

 

Maximum Current at cut-off voltage

 

 

 

 

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

96 ADC

120 ADC

154 ADC

189 ADC

235 ADC

294 ADC

353 ADC

86-160310-00 E00

System Description and Specifications

1 — 9