Installation and User Manual

2.4.2Mechanical

The Comet UPS can be mounted on a raised computer room floor, or flush-mounted on a concrete floor. All floors must be level. On a raised floor, conduits can be run below the floor, with cut-outs made in the floor tiles as shown on the installation drawings.

Allow at least three feet of clearance in front of the UPS for normal operation (access to the UPS controls). The Comet requires at least 36 inches top clearance for ventilation.

2.4.3Electrical

Electrical service for the Comet UPS should be supplied on its own dedicated branch circuit. Main input cables and upstream protective devices must be provided and sized per the National Electrical Code (NEC, ANSI/NFPA 70, latest issue), and as appropriate for your load and distribution requirements. Cable sizing data is provided on the installation drawings supplied with the equipment. The Comet 480/480V UPS is not a separately-derived source. The Comet 208/208V UPS is a separately derived source. The neutral must be grounded on a separately derived source (like the Comet 208/208V UPS).

CAUTION

The customer supplied upstream protective device shall open in one cycle

 

when 10 times the output rated current is applied or in the event of an output

 

short circuit when the unit is working on “Static Switch.”

 

Refer to the upstream circuit breaker manufacturer’s characteristic curves for

 

proper trip settings.

 

 

 

Table 2-1: Recommended upstream protective device sizing *.

INPUT VOLTAGE

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

 

 

 

 

 

 

 

 

 

 

208

150A

175A

225A

300A

350A

450A

500A

 

 

 

 

 

 

 

 

 

 

220

150A

175A

225A

300A

350A

450A

500A

 

 

 

 

 

 

 

 

 

 

480

70A

80A

100A

125A

150A

200A

225A

 

 

 

 

 

 

 

 

 

 

600

60A

70A

80A

100A

125A

150A

200A

 

 

 

 

 

 

 

 

 

 

* Size determined using nominal input currents.

86-160310-00 E00

Installation

2 — 3

Page 28