1.8Technical data

1.8.1 Configuration

The user can configure the card with one of the following means:

ZWeb browser

ZLocal serial link

ZTelnet console

ZBOOTP/DHCP

ZMupgrade

1.8.2 Administration

ZUp to 50 workstations protected

ZUp to 15 browsers connected at the same time

ZE-mail sending configurable according to UPS alarms and transmission of a periodical report

ZMeasurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting down the installation

ZControl of UPS on/off switching via the HTML interface

ZAdjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and optimisation of backup time by shutting down non-priority systems

ZAdjustment of date and time via NTP server - Daylight Saving Time management

ZProtection by encrypted password.

ZProtection by secured connection SSL and SSH

ZSaving of logs in the non-volatile memory

ZAutomatic language detection according to browser configuration.

ZLanguages available: English / French / Spanish / German / Italian

ZOn-line help available for each page

ZCard firmware updated via the network

ZCard configuration deployment on your installed base through network utility (Mupgrade)

1.8.3 Network

ZFast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet

ZSNMP trap port modifiable (by default = 162)

1.8.4 MIB (Management Information Base)

ZMIB IETF UPS (RFC1628) / MIB MGE V1.7

1.8.5 Environment sensor

ZTemperature measurement from 0 to 70 °C with +/- 1°C accuracy

ZMeasurement of humidity from 0 to 100 % with +/- 6 % accuracy

ZMin / max time-stamped function for temperature and humidity

ZChoice of temperature readings in Celsius or Fahrenheit

ZHigh and low thresholds, hysteresis and offset adjustable via Web interface

ZPossibility of notification of status changes by e-mail, SMS or SNMP traps

ZPosition detection of 2 dry contacts (maximum sensor/contact distance: 20 m)

ZName and status of each configurable contact