7.6Single UPS Shutdown Sequence

Typical example of the backup time provided by a UPS connected to Network Management Card:

As soon as it detects the loss of AC power, the Mgt. Card notifies the Network

1Shutdown Modules that the system is running on battery power.

The Mgt. Card then continuously monitors the criteria set to trip the shutdown

2procedure. The procedure is launched if:

1.the shutdown time delay (*) (in seconds), started when the loss of AC power occurred, expires.

2.the UPS battery level drops below (*) a threshold expressed in %.

3.the UPS backup time drops below (*) a threshold expressed in seconds.

4.the UPS backup time reaches the maximum value of the "shutdown duration" parameters 6

 

The Mgt. card centralizes the "shutdown duration" parameters for all the protected

 

computers (machines hosting Network Shutdown Module).

 

This fourth tripping criterion is implicit.

 

 

3

The Mgt. Card launches the shutdown procedure:

The Mgt. Card sends to all the Network Shutdown Modules the system shutdown order.

 

As a result, each Network Shutdown Module proceeds with shutdown of its system.

4

Once all the computers have been shut down, the UPS shuts off (interrupts the supply

of power to the loads) to protect the battery.

 

Note. This function is not authorized on some UPSs.

5

Once the utility is restored, the UPS restarts all computers (if shut off the UPS output is

a function available).

The diagrams below present the sequence.

Utility

Output

Network

Management

Card Sequence

Utility failure

Shutdown condition

Shutdown

Utility restored

1

3

4

5

2

Maximum 6 shutdown duration

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Shutdown Module V3 – User Manual - APC # 990-3630 (MGE # 34 003 934 XU / AB)

Page 44/66

Page 45
Image 45
MGE UPS Systems Network Shutdown Module V3 user manual Single UPS Shutdown Sequence, Diagrams below present the sequence

Network Shutdown Module V3 specifications

The MGE UPS Systems Network Shutdown Module V3 is an advanced solution designed to manage the safe shutdown of critical IT infrastructures during power outages. As businesses increasingly rely on electronic systems for their operations, ensuring data integrity and preventing hardware damage during unexpected shutdowns is paramount. The Network Shutdown Module V3 provides a seamless response to power loss events, ensuring that systems are properly powered down, minimizing the risk of data loss and equipment failure.

One of the key features of the MGE UPS Systems Network Shutdown Module V3 is its multi-platform support, which allows it to be compatible with various operating systems, including Windows, Linux, and Unix. This versatility ensures that organizations can integrate the module into their existing IT environments without the need for extensive modifications. Additionally, the software can manage multiple servers simultaneously, making it an ideal solution for data centers and enterprises with distributed IT systems.

The module employs advanced communication protocols, including SNMP and Web-based interfaces, facilitating easy integration with network management systems. This feature enables IT administrators to monitor UPS status in real-time, allowing for proactive responses to potential power issues. Furthermore, the Network Shutdown Module V3 can send notifications to users and administrators via email or SNMP traps, keeping everyone informed during critical power events.

Another significant benefit of the Network Shutdown Module V3 is its user-friendly configuration options. The intuitive web interface simplifies setup and management, allowing users to customize shutdown settings according to their specific needs. The module can be configured to initiate a graceful shutdown sequence that saves work in progress and performs necessary tasks, such as database backups, before the systems power down.

The Network Shutdown Module V3 is built with robust security features to protect sensitive data during power interruptions. It includes encryption for data transmission and access controls to ensure that only authorized personnel can make changes to the shutdown settings. This focus on security helps organizations comply with industry standards and regulations, further enhancing the module's value.

In conclusion, the MGE UPS Systems Network Shutdown Module V3 is an essential component for any organization seeking to safeguard its electronic systems against power failures. With its multi-platform support, advanced communication capabilities, user-friendly interface, and robust security features, this module ensures that businesses can maintain operational continuity and protect valuable data even in the face of unexpected power disruptions.