7.7Multi UPS shutdown sequence (example with Static Transfer Switch)

Typical example of the backup time provided by 2 UPSs in redundancy through Static Transfer Switch.

ωThe Output load level of the first UPS is less than 50 %.

ωThe Output load level of the second UPS is 0 %.

1

As soon as they detect the loss of AC power, the Mgt. Cards notify the Network

Shutdown Modules that the system is running on battery power.

 

 

2

The Network Shutdown Modules continuously compute the “minimum number of

necessary UPSs”.

 

In this case we suppose that the minimal number is 1.

 

When the first UPS stops its output, the Static Transfer Switch balances the load on the

 

second UPS. Then we are in a typical « single UPS sequence »

3

ω The Mgt. Card launches the shutdown procedure for UPS 2.

ω As a result, each Network Shutdown Module proceeds with the shutdown of its

 

 

system.

 

 

4

Once all the computers have been shut down, the UPS shuts off (interrupts the supply of

power to the loads) to protect the battery.

 

Note: This function is not authorized on some UPSs.

5

Once the utility is restored, the UPS restarts all computers (if the shutting off the UPS

output function available).

The diagrams below present the sequence.

Utility

UPS1 Output

UPS2 Output

Shutdown Mod powered by STS

Utility Failure Shutdown

UPS1

Shutdown

UPS 2

Utility Restored

criteria on

Shutoff

criteria on

Shutoff

UPS1

 

UPS2

 

 

 

 

1

 

3

4

5

2

System Shutdown 6

Duration

Load powered

Load

Load

Load powered

by UPS1

powered by

unpowered by UPS1

 

UPS2

 

 

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R

Network Shutdown Module V3 – User Manual - APC # 990-3630 (MGE # 34 003 934 XU / AB)

Page 46/66

Page 47
Image 47
MGE UPS Systems Network Shutdown Module V3 user manual UPS1

Network Shutdown Module V3 specifications

The MGE UPS Systems Network Shutdown Module V3 is an advanced solution designed to manage the safe shutdown of critical IT infrastructures during power outages. As businesses increasingly rely on electronic systems for their operations, ensuring data integrity and preventing hardware damage during unexpected shutdowns is paramount. The Network Shutdown Module V3 provides a seamless response to power loss events, ensuring that systems are properly powered down, minimizing the risk of data loss and equipment failure.

One of the key features of the MGE UPS Systems Network Shutdown Module V3 is its multi-platform support, which allows it to be compatible with various operating systems, including Windows, Linux, and Unix. This versatility ensures that organizations can integrate the module into their existing IT environments without the need for extensive modifications. Additionally, the software can manage multiple servers simultaneously, making it an ideal solution for data centers and enterprises with distributed IT systems.

The module employs advanced communication protocols, including SNMP and Web-based interfaces, facilitating easy integration with network management systems. This feature enables IT administrators to monitor UPS status in real-time, allowing for proactive responses to potential power issues. Furthermore, the Network Shutdown Module V3 can send notifications to users and administrators via email or SNMP traps, keeping everyone informed during critical power events.

Another significant benefit of the Network Shutdown Module V3 is its user-friendly configuration options. The intuitive web interface simplifies setup and management, allowing users to customize shutdown settings according to their specific needs. The module can be configured to initiate a graceful shutdown sequence that saves work in progress and performs necessary tasks, such as database backups, before the systems power down.

The Network Shutdown Module V3 is built with robust security features to protect sensitive data during power interruptions. It includes encryption for data transmission and access controls to ensure that only authorized personnel can make changes to the shutdown settings. This focus on security helps organizations comply with industry standards and regulations, further enhancing the module's value.

In conclusion, the MGE UPS Systems Network Shutdown Module V3 is an essential component for any organization seeking to safeguard its electronic systems against power failures. With its multi-platform support, advanced communication capabilities, user-friendly interface, and robust security features, this module ensures that businesses can maintain operational continuity and protect valuable data even in the face of unexpected power disruptions.