3. Operation
"Output" tab
Personalisable function | Default setting | Options |
|
|
|
Rated UPS voltage | 230 V | 200 V - 208 V - 220 V - 240 V |
|
|
|
Rated UPS frequency | F = 50 Hz | 60 Hz |
|
|
|
UPS tolerance for | F ± 5% | F ± 1% to ± 10%, in 1% steps |
source frequency |
|
|
|
|
|
Overload alarm threshold | 110% | 0 to 110%, in 10% steps |
|
|
|
UPS restart following | Disabled | Enabled (click to add check) |
|
|
|
"Bypass" tab
Personalisable function | Default setting | Options |
|
|
|
Transfer to bypass if overload | Enabled | Disabled (click to remove check) |
|
|
|
Transfer to bypass following a fault, whatever the | Disabled | Enabled (click to add check) |
conditions on the |
|
|
|
|
|
3.5 Shutdown
Press button 23 (return to the OFF position).
The connected equipment is no longer supplied with power.
23
Page 20 - 51031604EN/AA