4. Maintenance

4.1 Troubleshooting

If any of LEDs 12 , 13 or 14 flash, there is a operating anomaly or an alarm.

If a LED flashes, the bargraph data is no longer displayed.

Troubleshooting not requiring MGE UPS SYSTEMS after-sales support

Indication

LED 12 flashes and the buzzer beeps.

LED 14 flashes.

Signification

UPS overload. Overload is too long or too high. The buzzer sounds continuously.

If AC power is present and within tolerances, the UPS goes to bypass mode (supply directly by the AC-power source). LED 20 flashes.

If AC power is not present or not within tolerances, the connected applications are no longer supplied.

A battery fault was detected during the automatic battery test.

Correction

Check the power drawn by the equipment and disconnect any non- priority devices.

Connect that the battery connector is fully pushed in.

Replace battery module (see the Maintenance section).

Troubleshooting requiring MGE UPS SYSTEMS after-sales support

Indication

Signification

Correction

 

 

 

LED 13 flashes and the

UPS electronics have detected a UPS fault.

 

buzzer sounds

Depending on the UPS personalisation parameters

 

(see section 3.4), there are two possibilities:

 

continuously.

 

 

 

the equipment connected to the UPS continues to be

supplied, but directly from the AC-power source (via

Call the after-sales support

department.

the automatic bypass (LED 20 ON);

 

the connected equipment is no longer supplied.

The equipment connected to the UPS is no longer protected.