Appliance dimensions
Do not install this exhaust hood over cooktops burning solid fuel.
When installing the hood, make sure that the following minimum distance (S) between the top of a Miele cooking surface and the bottom of the hood is:
-22" (55 cm) above electric cooktops
-26" (65 cm) above gas cooktops
-26" (65 cm) above an open grill
For
If there is more than one appliance beneath the hood and they have different minimum safety distances always select the greater distance.
See "Warning and Safety instructions" for further information.
26" (65 cm) is recommended for all installations to allow for optimum work space under the hood.
Read the entire installation procedures and determine height (S) before beginning the installation. Installation producers differ depending on the model and venting method.
If the hood is fitted flush to the ceiling make sure that the remaining distance to the ceiling is not greater or less than appliance height H.
Standard unit height H:
DA 211
Extraction. . . . . . . . . . . . 29 1/8" - 38 9/16"
. . . . . . . . . . . . . . . . . . . (740 - 980) mm
Recirculation . . . . . . . 32 11/16" - 41 15/16"
. . . . . . . . . . . . . . . . . . (830 - 1065 mm)
DA
Extraction . . . . . . . . . . . . . 28" * - 37 3/8"
. . . . . . . . . . . . . . . . . . . (710* - 950) mm
Recirculation . . . . . . . . . . 31 1/2" - 40 3/4"
. . . . . . . . . . . . . . . . . . (800 - 1035 mm)
DA 218
Extraction . . . . . . . . . . . . 28 1/8" - 37 5/8"
. . . . . . . . . . . . . . . . . . . (715 - 955) mm
Recirculation . . . . . . . 31 11/16" - 40 15/16"
. . . . . . . . . . . . . . . . . . (805 - 1040 mm)
DA
Extraction. . . . . . . . . . . . 28 3/4" - 38 3/16"
. . . . . . . . . . . . . . . . . . . (730 - 970 mm)
Recirculation . . . . . . . . 32 5/16" - 41 9/16"
. . . . . . . . . . . . . . . . . . (820 - 1055 mm)
*With air extraction to the rear through
a wall the total height must be at least 31 1/8" (790 mm).
To fit the chimney, distance A between the top of the chimney and the ceiling must be at least 7/8" (20 mm).
Cut out area in wall or ceiling for entrance of 6" (150 mm) ductwork or 5" (125 mm)
ductwork with a reducing collar.
29