2-10. Connecting To 115 Volts AC Duplex Receptacle

3

2

1

1115 V 15 A AC Receptacle RC9

Power is shared between RC9 and remote 14 receptacle RC8.

2Circuit Breaker CB1

3Circuit Breaker CB2

CB1 protects 115 volts ac portion of RC8 and RC9 from overload.

CB2 protects 24 volts ac portion of RC8 from overload.

Press button to reset breaker.

Ref. ST-801 380-B

2-11. Electrical Service Guide

60 Hertz Models

250 Amp Model

 

300 Amp Model

 

 

 

 

 

 

 

 

 

Input Voltage

200

230

460

200

230

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

34.5

30

15

38

33

16.5

13

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Or Circuit

50

45

20

60

50

25

20

Breaker Rating In Amperes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Input Conductor Size In AWG/Kcmil

8

10

14

8

8

12

14

 

 

 

 

 

 

 

 

Max Recommended Input Conductor Length In Feet

116 (35)

100 (31)

157 (48)

105 (32)

139 (42)

221 (67)

223 (68)

(Meters)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

10

10

14

10

10

12

14

 

 

 

 

 

 

 

 

Reference: 1996 National Electrical Code (NEC)

 

 

 

 

 

 

S-0092-J

 

 

 

 

 

 

 

 

50 Hertz Models

 

200 Amp Model

 

 

300 Amp Model

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

220

380

400

440

520

220

380

400

440

520

 

 

 

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

19.1

12

10.5

9.5

8.8

34.5

20

19

17.3

14.6

 

 

 

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Or

30

20

15

15

15

50

30

30

25

20

Circuit Breaker Rating In Amperes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Input Conductor Size In AWG/Kcmil

10

14

14

14

14

8

12

12

12

14

 

 

 

 

 

 

 

 

 

 

 

Max Recommended Input Conductor

146

171

189

229

320

127

151

167

202

183

Length In Feet (Meters)

(44)

(52)

(58)

(70)

(97)

(39)

(46)

(51)

(62)

(56)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/

10

14

14

14

14

10

12

12

12

14

Kcmil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference: 1996 National Electrical Code (NEC)

 

 

 

 

 

 

 

 

 

S-0092-J

 

 

 

 

 

 

 

 

 

 

 

OM-259 Page 15