2-11. Electrical Service Guide

Input Voltage

200

230

 

 

 

Input Amperes At Rated Output

30

26

 

 

 

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

 

 

Circuit Breaker 1, Time-Delay 2

35

30

Normal Operating 3

45

40

Min Input Conductor Size In AWG/Kcmil

10

10

 

 

 

Max Recommended Input Conductor Length In Feet (Meters)

97

128

(29)

(39)

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

10

10

 

 

 

Reference: 1999 National Electrical Code (NEC)

1Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

YCaution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.

2-12. Selecting A Location And Connecting Input Power

18 in (457 mm) of space for airflow

Y Do not move or operate unit where it could tip.

Y Always connect grounding conductor first.

= GND/PE

5

L1

L2

1 Rating Label

Supply correct input power.

2Plug

3Receptacle

Connect plug to receptacle.

4Input And Grounding Conductors

Connect directly to line disconnect device if hard wiring is required.

5Line Disconnect Device See Section 2-11.

YSpecial installation may be required where gasoline or volatile liquids are present – see NEC Article 511 or CEC Section 20.

1

1

2

4

3

L2L1

230 VAC, 1

801 568 / Ref. 800 797-B

OM-1313 Page 10

Page 14
Image 14
Miller Electric OM-1313 manual Electrical Service Guide, Selecting a Location And Connecting Input Power, Input Voltage