General Specifications

General Specifications

Notes: For MS/MSH, MF, MSM

*1. Rating conditions (cooling)_____ Indoor: 80˚F DB, 67˚F WB Outdoor: 95˚F DB, 75˚F WB

(heating)_____ Indoor: 70˚F DB, 60˚F WB Outdoor: 47˚F DB, 43˚F WB

*2. Include auxiliary electric heater operations at 115V. (MSH09EW, MSH12EN, MSH15EN)

*3. Rated voltage of compressor and fan motor is 115V. (MUM18EW)

*4. Values are for each indoor unit.

*5. Depth of outdoor unit ( ) includes thickness of fan grille.

Operating Range

MODEL

Indoor air intake temperature

Outdoor air intake temperature

Cooling

Maximum

95˚F DB, 71˚F WB

115˚F DB

Minimum

67˚F DB, 57˚F WB

67˚F DB

 

Heating

Maximum

80˚F DB, 67˚F WB

75˚F DB, 65˚F WB

Minimum

70˚F DB, 60˚F WB

17˚F DB, 15˚F WB

 

Notes: For PK/PKH, PC/PCH, PL/PLH

*1. Rating conditions (cooling)_____ Indoor: 80˚F DB, 67˚F WB Outdoor: 95˚F DB, 75˚F WB (heating)_____ Indoor: 70˚F DB, 60˚F WB Outdoor: 47˚F DB, 43˚F WB

*2. Rating conditions (heating)_____ Indoor: 70˚F DB, 60˚F WB Outdoor: 17˚F DB, 15˚F WB

*3. Heating capacity and power consumption in [ ] include auxiliary electric heater operation at 208/230V.

Operating Range

MODEL

Indoor air intake temperature

Outdoor air intake temperature

Cooling

Maximum

95˚F DB, 71˚F WB

 

115˚F DB

Minimum

67˚F DB, 57˚F WB

*5

0˚F DB

 

Heating

Maximum

80˚F DB, 67˚F WB

75˚F DB, 65˚F WB

Minimum

70˚F DB, 60˚F WB

17˚F DB, 15˚F WB

 

*5 With Wind Baffle installed.

REFRIGERANT TUBING SIZE

 

 

 

Refrigerant Tubing

 

 

 

MODEL

 

 

 

 

 

 

Connection

 

Max. Height

Max. Tubing

 

Tubing (OD)/N

 

 

Method

 

 

Difference (ft)

Length (ft)

 

Liquid

Gas

 

MS09EW, MSH09EW, MSM18EW

25

49

 

 

3/8

 

MF12EN, MF15EN

 

 

 

1/2

 

 

 

 

 

 

 

MSM30EN

MS09EW

25

65

 

1/4

3/8

 

(MS09EWX2•MS15ENX1)

MS15EN

 

 

5/8

 

 

 

 

 

 

 

 

 

 

 

 

 

MS12EN, MS15EN, MSH12EN, MSH15EN

25

49

 

 

 

 

 

 

 

PK18EK, PKH18EK, PL18FK, PLH18FK,

130

130

 

 

 

Flared

PK12EK, PL12FK

 

 

 

 

3/8

5/8

 

PK24EK, PKH24EK, PC24EK, PCH24FK,

 

 

 

 

 

 

 

 

 

 

PL24FK, PK24EK

 

 

 

 

 

 

 

 

 

164

164

 

 

 

 

PK30EK, PKH30EK, PL30FK, PLH30FK,

 

 

 

 

 

 

 

 

 

 

PC30EK, PCH30EK, PL36FK, PLH36FK,

 

 

 

1/2

3/4

 

PC36EK, PCH36EK, PL42FK2, PC42EK

 

 

 

 

 

 

 

 

 

 

PLH42FK, PCH42EK

 

 

 

 

 

7/8

 

 

 

 

 

 

 

 

 

*For more details refer to Technical And Service Manual. All specifications are subject to change without notice.

MITSUBISHI ELECTRONICS AMERICA, INC.

HVAC DIVISION

3100 AVALON RIDGE PL. STE. 200, NORCROSS, GA 30071

 

CALL: 770-613-5840 OR 800-433-4822 (PRESS 3) FAX: 800-889-9904

Form No. MIT-MRS-24-97

Page 11
Image 11
Mitsubishi PCH36EK Model, General Specifications, Operating Range, Refrigerant Tubing Size, Notes: For MS/MSH, MF, MSM