13. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions:
SM
NV
Ig1 Iga Ig2 Igm
Servo
amplifier
MR-E-40A
2mm2 5m 2mm2 5m
Servo motor
HC-KFE73
Use a leakage current breaker generally available.
Find the terms of Equation (13.2) from the diagram:
Ig1 20 100050.1 [mA]Ig2 20 100050.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (13.2):
Ig 10 {0.1 00.1 1(0.1 0.1)}
4.0 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/SW/CP/CW/HW series.