OPERATION INDICATOR Lighted
Blinking
Not lighted
·Flashing of OPERATION INDICATOR lamp
·OPERATION INDICATOR lamp
No. | Abnormal | Operation indicator lamp | Symptom |
| point |
|
|
| MXZ type | Right lamp flash | Outdoor unit |
1 | Operation |
| operates but |
| indoor unit | ||
mode |
| ||
| does not | ||
| setting | ||
|
|
| operate. |
Condition
The operation mode of the each indoor
unit is differently set to COOL(includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at first has the priority.
Correspondence
•Unify the operation mode. Refer to outdoor unit service manual.
8-5. Trouble criterion of main parts
Part name
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Check method and criterion | Figure |
Measure the resistance with a tester.
Refer to
"Indoor electronic control P.C. board", the chart of thermistor.
Indoor fan motor(MF) | Check |
|
|
| |
Horizontal vane | Measure the resistance between the terminals with a tester. | RED |
| ||
(Part temperature 50° F ~ 86° F) | ROTOR | ||||
motor(MV) | |||||
|
| YLW |
| ||
Color of the lead wire | Normal |
| |||
BRN |
| ||||
| |||||
235 " ~ 255 " |
|
| |||
| ORN | GRN | |||
|
|
| |||
Horizontal vane | Measure the resistance between the terminals with a tester. | RED |
| ||
motor(MV1) |
| ||||
(Part temperature 50° F ~ 86° F) | ROTOR | ||||
Vertical vane |
|
| YLW |
| |
motor(MV2) | Color of the lead wire | Normal |
| ||
BRN |
| ||||
282 " ~ 306 " |
|
| |||
| ORN | GRN | |||
|
|
17