Mitsubishi Electronics MSZ-A12NA, MSY-A24NA How to check mis-wiring and serial signal error

Models: MSY-A15NA MSZ-A09NA MSZ-A17NA MSZ-A12NA MSZ-A24NA MSZ-A15NA MSY-A24NA MSY-A17NA

1 48
Download 48 pages 11.54 Kb
Page 21
Image 21

When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch. Indoor unit does not operate.

When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second. Outdoor unit does not operate.

DHow to check mis-wiring and serial signal error

Turn OFF the power supply.

Is there rated voltage AC

No

in the power supply?

 

Yes

 

Turn ON the power supply.

Check the power supply.

 

 

 

Is there rated voltage between

No

 

 

 

 

 

Check the wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor terminal block S1 and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S2?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press EMERGENCY OPERATION switch once.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the left lamp of OPERATION INDICATOR

 

 

 

 

 

 

 

 

 

 

lamp light up?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

<Confirmation of the power to the indoor unit>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Is there any mis-wiring,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is serial signal error indicated 6 minutes later?

 

 

 

No

poor contact, or wire

Yes

 

 

 

 

 

 

 

 

 

 

 

 

disconnection of the

 

 

 

Correct them.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor/outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

connecting wire?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn OFF the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check once more if the indoor/outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

connecting wire is not mis-wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Short-circuit outdoor terminal block S2 and

 

 

W1. Mis-wiring may damage indoor electronic control

 

 

 

S3.

 

 

 

 

 

P.C. board during the operation.

 

 

 

 

 

 

 

 

W1

 

 

 

 

 

Be sure to confirm the wiring is correct before the

 

 

 

 

 

 

 

 

 

 

 

operation starts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W3.Be sure to check this within 3 minutes after turning

 

 

 

 

 

 

 

 

 

 

 

ON. After 3 minutes, LED blinks 6 times. Even when

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the power supply.

 

 

 

 

 

the inverter P.C.board or the outdoor electronic control

 

 

 

 

 

 

 

 

 

 

 

P.C.board is normal, LED blinks 6 times after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Except for outdoor unit of multi system type)

 

 

Does the LED on the inverter P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

Replace the inverter P.C. board or

 

 

 

 

or the outdoor electronic control P.C.board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the outdoor electronic control P.C.board.

 

 

 

repeat "3.6-second-OFF and 0.8-second-ON (Lighted or

 

 

 

 

W2

 

 

 

 

 

 

 

quick blinking"? W3

 

 

not lighted)

 

 

 

 

 

 

 

 

 

 

 

 

 

W2 Be careful to the residual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

voltage of smoothing capacitor.

A

·Turn OFF inverter-controlled lighting equipment.

·Turn OFF the power supply and then turn ON again.

·Press EMERGENCY OPERATION switch.

Turn OFF the power supply.

 

 

 

Remove the short-circuit between

 

Is there any error of the

outdoor terminal block S2 and S3.

 

indoor/outdoor connecting wire,

Turn ON the power supply.

 

 

 

such as the damage of the wire,

Is there amplitude of 10 to 20V DC

 

No intermediate connection, poor

between outdoor terminal block S2

and S3? <Confirmation of serial

 

contact to the terminal block?

signal>

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Is there any error of the

Is there rated voltage between

 

indoor/outdoor connecting wire,

indoor terminal block S1 and S2?

 

such as the damage of the wire,

Yes

Yes

Replace the indoor/outdoor connecting wire.

Replace the

Is serial signal

No

error indicated

 

6 minutes later?

 

·Reinstall either the unit or the light each other away.

·Attach a filter on remote control

<Confirmation of power voltage>

intermediate connection, poor

 

contact to the terminal block?

 

No

Yes

No

 

indoor/outdoor connecting wire.

Yes

B

receiving section of the indoor unit.

Replace the indoor electronic control P.C. board.

Be sure to release the failure-mode recall function after checking.

Refer to outdoor unit service manual.

21

Page 21
Image 21
Mitsubishi Electronics MSZ-A12NA, MSY-A24NA, MSY-A15NA, MSY-A17NA, MSZ-A17NA How to check mis-wiring and serial signal error