Mitsubishi Electronics MSY-A17NA, MSY-A24NA Check of indoor fan motor, Troubleshooting flow

Models: MSY-A15NA MSZ-A09NA MSZ-A17NA MSZ-A12NA MSZ-A24NA MSZ-A15NA MSY-A24NA MSY-A17NA

1 48
Download 48 pages 11.54 Kb
Page 18
Image 18

8-6. Troubleshooting flow

When OPERATION INDICATOR lamp flashes 3-time. Indoor fan does not operate.

A Check of indoor fan motor

The indoor fan motor error has occurred, and the indoor fan doesn't operate.

Turn OFF the power supply.

Is there any foreign matter that interferes the rotation of the line flow fan?

Yes

Remove the foreign matter and adjust the line flow fan.

No

Pay careful attention to the high voltage on the fan motor connector CN211.

Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.

Measure the supply voltage as follows within 12 seconds after EMERGENCY OPERATION switch is pressed.

If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage. w

1.Measure the voltage between CN211 1(+) and 3(-). 2.Measure the voltage between CN211 5(+) and 3(-).

wIf more than 12 seconds or more passes after EMERGENCY OPERATION switch is pressed, the voltage mentioned above 2 goes 0V DC although the indoor electric control P.C. board is normal.

Is there 294/325V DC between

 

 

 

CN211 1 (+) and 3 (-), and does

 

 

 

the voltage between CN211 5(+)

Yes

 

and 3(-) rise to the range of 3 to 6V

 

 

Replace the indoor fan motor.

 

DC within 12 seconds after

 

 

 

 

 

 

EMERGENCY OPERATION switch

 

 

 

is pressed?

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

Indoor electronic control P.C. board

CN211

Replace the indoor electronic control P.C. board.

The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3times, and then stops.

Measure the voltage between CN211 6(+) and 3(-) while the fan

motor is rotating.

 

No

Is it unchanged holding

(Changed)

Replace the indoor electronic control P.C. board.

0V DC or 15V DC?

 

Yes (Unchanged)

Replace the indoor fan motor.