Mitsubishi Electronics MSZ-D30/36NA Indoor Unit Installation, Attaching The Installation Plate

Models: MSZ-D30/36NA MSY-D30/36NA

1 8
Download 8 pages 44.28 Kb
Page 4
Image 4
2. INDOOR UNIT INSTALLATION

2. INDOOR UNIT INSTALLATION

2-1. ATTACHING THE INSTALLATION PLATE

Find a stud in the wall to attach installation plate (1) horizontally on the wall with screws (2).

To prevent installation plate (1) from vibrating, be sure to install the attachment screws in the holes indicated in the illustration. For added support, additional screws may also be installed in other holes.

‡ ,IWKHUHFHVVHGEROWLVWRRORQJFKDQJHLWIRUDVKRUWHURQH ¿HOGVXSSOLHG 

2-2. DRILLING

1)Determine where the holes will be located on the wall.

2)Drill a ø 3 in. (75 mm) hole. The outdoor side should be 6/32 to 9/32 in. (5 to 7 mm) lower than the indoor side.

3)Insert wall hole sleeve (C).

2-3. CONNECTING WIRES FOR INDOOR UNIT

Note:

When the indoor unit is powered from the outdoor unit, depending on local code, a discon- nect switch needs to be installed to a power supply circuit.

1)Open the front panel.

2)Place the upper part of the indoor unit on the installation plate.

3)Remove electrical cover.

4)Remove VA clamp.

5)Remove corner box.

6)Remove cable guide.

7)Remove conduit plate.

8)Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward piping) to conduit plate with lock nut. The thread of the installed conduit pipe / elbow joint appear- ing inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less than 1-3/16 in. (30 mm) outside. (Fig. 2)

9)Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical parts box.

10)Process the end of indoor/outdoor unit connecting wire (A) (Fig.3). Attach it to the terminal block. Be careful not to make mis-wiring. Attach the wire to the terminal block securely so that its core cannot be seen, and no external force affects the connecting section of the terminal block.

11)Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fas- tened.

12)Reinstall conduit plate.

13)Reinstall cable guide.

14)According to the piping direction, remove the shaded part of the left side of box (Fig.4) or corner box (Fig. 5).

15)Reinstall VA clamp.

16)Reinstall electrical cover.

17)Reinstall panel assembly.

Remark:

INDOOR UNIT

Grounding

* A disconnect switch is required.

 

Check the local code.

Terminal block

terminal**

** Use a ring tongue terminal in

 

 

order to connect a ground wire

 

 

to terminal.

 

Disconnect

 

 

 

208/230 V AC

switch*

 

 

 

1phase, 60 Hz

 

OUTDOOR UNIT

 

Power supply

Terminal 1block

 

208/230 V AC,

 

 

1phase 2 wires,

 

 

60 Hz

 

 

Ground

Grounding terminal**

 

 

 

Ceiling

2-13/16 in. (70 mm) or more

 

 

5-1/8 in. (130 mm) or more for left

 

 

 

and left back piping (using spacer)

 

Installation plate (1)

Level

 

 

 

 

 

 

 

4-11/16 in.

 

4 in.

8-11/16 in.

Wall

 

(100 mm)

(120 mm)

 

 

(220 mm) Wall

 

or more

 

 

or more

 

 

 

 

 

Attachment screw (2)

Insert

Align the

Center of

 

 

the

 

 

scale. *

scale with

ø 3 in.

 

 

 

the line. *

(75 mm)

hole

* Same for left hole.

 

Wall

ø 3 in.

6/32-9/32 in.

(75 mm)

 

(5-7 mm)

 

Outdoor side

Electrical cover

Pull tab to remove cable guide.

VA Clamp

Electrical box

Indoor terminal block 2-1. ATTACHING THE INSTALLATION PLATE

 

Grounding

 

terminal

Cable guide

 

 

Conduit pipe

Conduit plate

or

 

Lock nut

 

• Connect wires to the appropri-

 

ate terminals

Elbow joint

For future servicing, leave some slack in the connecting wires.

Conduit plate

 

 

 

 

Less than 3/8 in.

 

 

 

(10 mm)

Conduit plate

 

 

Lock nut

Less than 1-3/16 in.

 

 

 

Conduit pipe or

 

 

 

(30 mm)

 

elbow joint

 

 

 

 

 

Elbow joint

 

Fig. 1

(for right, left, or downward piping)

 

 

Fig. 2

 

5/8 in.

 

 

2-3/16 in.

(15 mm)

 

 

(55 mm)

 

 

 

Lead

 

 

 

wire

 

 

 

• Make ground wire a little longer than

Remove panel

Box

 

others. (More than 1-9/16 in. [40 mm])

for piping on

Remove panel for piping

 

Fig. 3

left side of unit

on bottom left side of unit

 

 

Fig. 4

 

Corner box

 

 

Remove panel for

Remove panel

 

piping on bottom

for piping on right

 

side of unit

side of unit

Fig. 5

 

 

Page 4
Image 4
Mitsubishi Electronics MSZ-D30/36NA, MSY-D30/36NA Indoor Unit Installation, Attaching The Installation Plate, Drilling