Mitsubishi Electronics MSY-D30/36NA Purging Procedures, Leak Test, And Test Run, Flare Connection

Models: MSZ-D30/36NA MSY-D30/36NA

1 8
Download 8 pages 44.28 Kb
Page 7
Image 7
3-2. FLARE CONNECTION

 

 

Nut

 

A inch (mm)

 

Tightening torque

Pipe diameter

 

 

 

 

 

inch

Clutch

Clutch

Wing nut

 

ft•lb

inch (mm)

 

(mm)

type tool

type tool

type tool

N•m

 

 

(kgf•cm)

 

 

 

for R410A

for R22

for R22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø 1/4

(6.35)

1/4

 

 

 

13.7 to

10 to 13

 

 

0.06 to

(140 to

(17)

 

 

17.7

 

 

 

 

180)

 

 

 

 

 

0.08

 

 

 

 

 

 

 

 

 

 

3/8

 

 

(1.5 to

34.3 to

25 to 30

ø 3/8

(9.52)

 

 

2.0)

 

0.04 to

(350 to

(22)

 

 

41.2

 

 

0 to 0.02

 

420)

 

 

 

0.06

 

 

 

 

 

 

 

 

 

 

1/2

(0 to 0.5)

(1.0 to

 

49.0 to

36 to 42

ø 1/2

(12.7)

 

1.5)

 

 

0.08 to

(500 to

(26)

 

 

56.4

 

 

 

 

575)

 

 

 

 

 

0.10

 

 

 

 

 

 

 

 

 

 

5/8

 

 

(2.0 to

73.5 to

54 to 58

ø 5/8

(15.88)

 

 

2.5)

 

 

(750 to

(29)

 

 

 

78.4

 

 

 

 

 

800)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-2. FLARE CONNECTION

1)Cut the copper pipe as straight as possible with a pipe cutter. (Fig. 1, 2)

2)Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to avoid getting metal shavings into the piping. (Fig. 3)

 5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWVWKHQSXWWKHPRQSLSH

4)Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select A mm from the table according to the tool you use.

5)Check

‡ &RPSDUHWKHÀDUHGZRUNZLWK)LJ

‡ ,IÀDUHLVGHIHFWLYHFXWRIIWKHVHFWLRQDQGUHSHDWSURFHGXUH

 

 

Good

No good

 

 

Copper

 

 

 

 

pipe

 

 

 

 

 

Tilted

Uneven

Burred

 

Fig. 1

 

 

Fig. 2

Burr

Copper pipe

 

 

 

Spare reamer

 

 

 

 

Pipe cutter

 

 

 

 

 

 

Fig. 3

Flaring tool

 

 

 

 

 

 

Die

Copper pipe

 

 

 

 

Clutch type

Wing nut type

Flare nut

 

 

 

Fig. 4

 

Fig. 5

Smooth all around

Inside is shin-

 

 

 

ing without any

 

 

 

 

 

 

 

 

scratches.

 

 

 

Even length

 

 

 

 

all around

Fig. 6

 

 

 

3-3. PIPE CONNECTION

‡ )DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOHDERYH

‡ :KHQIDVWHQHGWRRWLJKWÀDUHQXWPD\HYHQWXDOO\EUHDNDQGFDXVHUHIULJHUDQWOHDNDJH

Indoor unit connection

Connect both liquid and gas piping to indoor unit.

• Apply a thin coat of refrigerant oil (J) on the seat surface of pipe.

‡ 7RFRQQHFW¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXW

• Use tightening torque table above as a guideline for indoor unit side joints, and tighten

XVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure detailed in Indoor unit connection.

• For tightening, use a torque wrench or spanner.

3-4. INSULATION AND TAPING

1)Cover piping joints with pipe cover.

2)For outdoor unit side, insulate the piping, including valves.

3)Apply piping tape (G) starting from the connection on the outdoor unit.

When piping has to be installed through a ceiling, closet or where the temperature

DQGKXPLGLW\DUHKLJKXVHDGGLWLRQDO¿HOGVXSSOLHGLQVXODWLRQWRSUHYHQWFRQGHQVD- tion.

4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN

4-1. PURGING PROCEDURES AND LEAK TEST

1)

Remove service port cap of stop valve on the side of the outdoor unit gas pipe.

2)

Connect gauge manifold valve and vacuum pump to service port of stop valve on the

 

gas pipe side of the outdoor unit.

3)

Run the vacuum pump 15 minutes or more.

4)

Check the vacuum with the gauge manifold valve, then close it and shut off the vacuum

 

pump.

5)

Leave as it is for one or two minutes. Make sure pointer gauge manifold valve remains

 

LQ WKH VDPH SRVLWLRQ &RQ¿UP WKDW SUHVVXUH JDXJH VKRZV ± 03D >*DXJH@ ±

 

LQ+J>±PP+J@ 

6)

Quickly remove gauge manifold valve from service port of stop valve.

7)

After refrigerant pipes are connected and evacuated, fully open all stop valves on both

 

sides of gas pipe and liquid pipe. Operating the unit without fully opening the valves

 

lowers the performance and causes problems.

8)

Refer to 1-3. SPECIFICATIONS, and charge the prescribed amount of refrigerant if

 

needed. Be sure to charge slowly with liquid refrigerant. Otherwise, composition of the

 

refrigerant in the system may be changed and affect performance of the air conditioner.

9)

Tighten cap of service port.

*4 to 5 turns

*Close

*Open 3-3. PIPE CONNECTION

Hexagonal wrench

Service port cap (Torque 13.7 to

17.7N•m, 140 to

180 kgf•cm)

Stop valve cap (Torque 19.6 to

29.4N•m, 200

WRNJIƒFP

±03D

±LQ+J

>±PP+J@

Stop valve for LIQUID

Handle

Low

Stop valve for

Indoor unit connection GAS

Adapter for pre- venting the back

ÀRZ

Compound pressure gauge (for R410A)

Pressure gauge Outdoor unit connection (for R410A)

Gauge manifold valve (for R410A)

Handle High

Charge hose (for R410A)

Vacuum pump (or the vacuum pump with the function to SUHYHQWWKHEDFNÀRZ

10) Conduct a leak test

Precautions when using the control valve

Service port

A3-4. INSULATION AND TAPING4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Control valve 4-1. PURGING PROCEDURES AND LEAK TESTManual backgroundManual background

Open Manual background

Close

Charge hose

Body

When attaching the control valve to the service port, valve core may deform or loosen if excess pressure is applied. This may cause gas leak.

When attaching the control valve to the service port, make sure that the valve core is in closed position, and then tighten part A. Do not tighten part A or turn the body when valve core is in open position.

Page 7
Image 7
Mitsubishi Electronics MSY-D30/36NA Purging Procedures, Leak Test, And Test Run, Flare Connection, Pipe Connection