6-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]

 

 

TIME SUN MON TUE WED THU FRI SAT

 

 

 

TIMER

Hr ON

 

 

 

AFTER

AFTER OFF

 

 

 

ERROR CODE

FUNCTION

 

ûFûC

 

ûFûC

FILTER

 

 

 

WEEKLY

 

 

ONLY1Hr.

 

SIMPLE

 

 

 

AUTO OFF

 

TEMP.

 

 

ON/OFF

 

MENU

ON/OFF

 

FILTER

BACK

MONITOR/SET

DAY

 

CHECK TEST

PAR-21MAA

CLOCK

OPERATION

CLEAR

<How to operate>

Press POWER ON/OFF button.

Press the operation MODE button to display AUTO. Press the TEMP. button to set the desired temperature.

NOTE: The set temperature changes 2°F when the

or

button is

pressed one time. Automatic 67 to 83°F

Control modes

 

Control details

Remarks

 

 

 

1. Initial value of

HEAT mode for room temperature < Desired temperature

 

operation mode

COOL mode for room temperature Desired temperature

 

 

 

 

2. Mode change

(1) HEAT mode → COOL mode

 

 

Room temperature

Desired temperature + 3°F. or 3 min. has passed

 

 

(2) COOL mode → HEAT mode

 

 

Room temperature

Desired temperature - 3°F. or 3 min. has passed

 

 

 

 

3. COOL mode

Same control as cool operation

 

 

 

 

4. HEAT mode

Same control as heat operation

 

 

 

 

 

6-6. WHEN UNIT IS STOPPED

Control modes

 

Control details

Remarks

 

 

 

 

1. Drain pump

1-1. Drain pump control

 

 

 

 

The drain pump turns ON for the specified amount of time when any of the following

 

 

conditions is met:

 

 

ON for 3 minutes after the operation mode is switched from COOL or DRY to

 

 

another operation mode (FAN).

 

 

ON for 6 minutes after the float switch is submerged in the water when the

 

 

float swich control judges the sensor is in the water.

 

 

 

 

 

 

1-2. Float switch control

· Same control

 

as COOL

 

• Float switch control judges whether the sensor is in the air or in the water by

 

operation

 

turning the float switch ON/OFF.

 

 

 

In the water : Detected that the float switch is ON for 15 seconds.

 

 

In the air

: Detected that the float switch is OFF for 15 seconds.

 

 

 

 

 