6-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]
|
| TIME SUN MON TUE WED THU FRI SAT |
| |
|
| TIMER | Hr ON |
|
|
| AFTER | AFTER OFF |
|
|
| ERROR CODE | FUNCTION | |
| ûFûC |
| ûFûC | FILTER |
|
|
| WEEKLY | |
|
| ONLY1Hr. |
| SIMPLE |
|
|
| AUTO OFF | |
| TEMP. |
|
| ON/OFF |
| MENU | ON/OFF |
| FILTER |
BACK | MONITOR/SET | DAY |
| CHECK TEST |
CLOCK | OPERATION | CLEAR |
<How to operate>
Press POWER ON/OFF button.
Press the operation MODE button to display AUTO.
Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the | or | button is |
pressed one time. Automatic 67 to 83°F
Control modes |
| Control details | Remarks |
|
|
| |
1. Initial value of | HEAT mode for room temperature < Desired temperature |
| |
operation mode | COOL mode for room temperature Desired temperature |
| |
|
|
| |
2. Mode change | (1) HEAT mode → COOL mode |
| |
| Room temperature | Desired temperature + 3°F. or 3 min. has passed |
|
| (2) COOL mode → HEAT mode |
| |
| Room temperature | Desired temperature - 3°F. or 3 min. has passed |
|
|
|
| |
3. COOL mode | Same control as cool operation |
| |
|
|
| |
4. HEAT mode | Same control as heat operation |
| |
|
|
|
|
6-6. WHEN UNIT IS STOPPED
Control modes |
| Control details | Remarks |
|
|
|
|
1. Drain pump |
| ||
|
| ||
| The drain pump turns ON for the specified amount of time when any of the following |
| |
| conditions is met: |
| |
| ON for 3 minutes after the operation mode is switched from COOL or DRY to |
| |
| another operation mode (FAN). |
| |
| ON for 6 minutes after the float switch is submerged in the water when the |
| |
| float swich control judges the sensor is in the water. |
| |
|
|
|
|
| · Same control | ||
| as COOL | ||
| • Float switch control judges whether the sensor is in the air or in the water by | ||
| operation | ||
| turning the float switch ON/OFF. | ||
|
| ||
| In the water : Detected that the float switch is ON for 15 seconds. |
| |
| In the air | : Detected that the float switch is OFF for 15 seconds. |
|
|
|
|
|
19