MICROPROCESSOR CONTROL
INDOOR UNIT CONTROL 6-1. COOL OPERATION
|
| TIME SUN MON TUE WED THU FRI SAT |
| |
|
| TIMER | Hr ON |
|
|
| AFTER | AFTER OFF |
|
|
| ERROR CODE | FUNCTION | |
| ûFûC |
| ûFûC | FILTER |
|
|
| WEEKLY | |
|
| ONLY1Hr. |
| SIMPLE |
|
|
| AUTO OFF | |
| TEMP. |
|
| ON/OFF |
| MENU | ON/OFF |
| FILTER |
BACK | MONITOR/SET | DAY |
| CHECK TEST |
CLOCK | OPERATION | CLEAR |
<How to operate> |
|
|
Press POWER ON/OFF button. |
|
|
Press the operation MODE button to display COOL. |
|
|
Press the TEMP. button to set the desired temperature. |
|
|
NOTE: The set temperature changes 2°F when the | or | button is |
pressed one time. Cooling 67 to 87°F |
|
|
Control modes |
| Control details | Remarks |
1. Thermoregulating |
| ||
function | • Room temperature | desired temperature + 2°F ···Thermo ON |
|
| • Room temperature | desired temperature ···Thermo OFF |
|
Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16 minutes from compressors start up,
Released condition : The timer which prevents reactivating is set for 3 minutes, and
Liquid pipe temp. (TH22) turns 50°F or above.
The condition of the thermo OFF has become complete by thermoregulating, etc.
The operation modes became mode other than COOL.
The operation stopped.
2. Fan | By the remote controller setting (switch of 4 speeds+Auto) | ||
|
|
|
|
|
| Type | Fan speed notch |
|
| 4 speeds + Auto type | [Low], [Med2], [Med1], [High], [Auto] |
| When [Auto] is set, fan speed is changed depending on the value of: | ||
| Room temperature - Desired temperature |
13