6. Electrical work
6.1.2. Separate indoor unit/outdoor unit power supplies (A-control application)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
1:1 System
S1
S2
L1
L2
GR GR
1
2
L1
L2
S1
S2
S3
S3
AB
C
G
D
B
E
F
S1
S2
L1
GR
L2
1
2
L1
L2
GR GR
S1
S2
S3
1
2
L1
L2
S1
S2
S3
S3
AB
C
D
GB
E
FF
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
AOutdoor unit power supply
BWiring circuit breaker or isolating switch
COutdoor unit
DIndoor unit/outdoor unit connecting cords
ERemote controller (Only for PKA-A·GA)
FIndoor unit
GIndoor unit power supply
Simultaneous twin system

If the indoor and outdoor units have separate power supplies, refer to the table at the

below. Change the indoor unit electrical box wiring refering to the figure in the right

and the DIP switch settings of the outdoor unit control board.

* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
AOutdoor unit power supply
BWiring circuit breaker or isolating switch
COutdoor unit
DIndoor unit/outdoor unit connecting cords
ERemote controller (Only for PKA-A·GA)
FIndoor unit
GIndoor unit power supply

ON

OFF 1 2 (SW8)

3

Indoor unit electrical box connector con-

nection change

Label affixed near each wiring diagram

for the indoor and outdoor units

Outdoor unit DIP switch settings (when

using separate indoor unit/outdoor unit

power supplies only)

Indoor unit specifications

Required

Required

*1.Max. 50 m, 165 ft
*2.The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft
*3.The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Use copper supply wires.

3. Use wires rated 300V or more for the power supply cables.

4. Install an earth longer than other cables.
Indoor unit model
Indoor unit power supply
Minimum circuit ampacity
Maximum rating of overcurrent protective device
Indoor unit power supply
Indoor unit power supply earth
Indoor unit-Outdoor unit *1
Indoor unit earth
Remote controller-Indoor unit *2
Indoor unit L1-L2 *3
Indoor unit-Outdoor unit S1-S2 *3
Indoor unit-Outdoor unit S2-S3 *3
Remote controller-Indoor unit *3
PKA
Single 208/230 V, 60 Hz
1 A
15A
2 × Min. AWG16
1 × Min. AWG16
2 × AWG22 (polar)
2 × AWG22 (Non-polar)
AC 208/230 V
DC24 V
DC12 V
Circuit
rating
Wiring
Wire No. × size
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)
Indoor unit power supplied from outdoor unit
(when shipped from factory)
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
Connectors
Indoor unit
control board
Separate indoor unit/outdoor unit power
supplies
Indoor unit
control board

* There are three types of labels (labels A, B, and C). Affix the appropriate labels to

the units according to the wiring method.

BG79U874H01_en 05.11.30, 9:238