Control modes Control details
1-1. Dry mode temperature is controlled by TH21.
Dry mode ON Room temperature ] desired temperature + 2°F
Dry mode OFF Room temperature [ desired temperature
1-2. Frozen prevention control
No control function
Indoor fan operation control depends on the compressor conditions.
3. Drain pump
1. Functions regulated
by temperature
Remarks
Room
temperature
3 min. passed since starting operation
Call
Room temperature (Ta)
Dry mode
ON
time (min)
Dry mode
OFF
time (min)
Less than 64°F
Over 64°FON
OFF
Ta ] 83°F
83°F > Ta ] 79°F
79°F > Ta ] 75°F
75°F > Ta
Unconditional
93
73
53
33
10
3
Dry mode OFF
2. Fan
Note: Remote controller setting is not acceptable.
Dry mode
Fan speed notch
ON
OFF
[Low]
Stop
4. Vane
(up/ down vane change)
Same control as COOL operation
Same control as COOL operation
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
8-2. DRY OPERATION
<How to operate>
1Press POWER ON/OFF button.
2Press the operation MODE button to display DRY.
3Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed once. Dry 67 to 87°F.
OC341B--1.qxp 07.7.11 1:29 PM Page 15