18
Control modes Control details
2. Fan
Remarks
2-3. Thermo OFF mode
When the thermoregulating function changes to OFF, the indoor fan operates in
[Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
No drain pump operation
However, when the control changes from COOL or DRY operation, the drain pump
operates for 3 minutes.
(1) Initial setting : OFF HEAT···[last setting]
When changing the mode from exception of HEAT to HEAT
operation ···[Downward C]
(2) Vane position :
Horizontal Downward A Downward B Downward CSwing
(3) Restriction of vane position
1 The vane is horizontally fixed for the following modes.
(The control by the remote controller is temporarily invalidated and controlled by
the unit.)
• Thermo OFF
• Stand by (hot adjust) [Extra low] mode
• Heat defrost mode
3. Drain pump
4. Vane control
(Up/ down vane
change)
From the preceding page