Monessen Hearth BUF500 for use of optional ak-4outside air kit, Basement Installation, Slab Floor

Models: BUF400 BUF500

1 20
Download 20 pages 43.44 Kb
Page 16
Image 16
for use of optional ak-4 outside air kit

for use of optional ak-4 outside air kit

Combustion Air

1.Locate combustion air assembly at an exterior location which is not likely to be accidentally blocked in any manner. Locate assembly a min. of 12" above the snow line to prevent blockage by snow accumulation.

2.Never mount the combustion air inlet assembly in a garage or storage area where combustible fumes such as gasoline might be drawn into the fireplace.

3.Combustion air can be drawn from the crawl space under a house when an adequate supply of air is provided by open ventilation.

4.CAUTION: Do not take combustion air from attic space or garage space.

5.Locate air supply inlet at least 3' away from any appliance vent terminal.

6.Avoid extremely long runs and numerous turns in the duct leading from the fireplace to the combustion air assembly. These conditions increase the resistance to the free flow of air through the duct. See Figures 14 through 17 for methods of installing the outside air for combustion assemblies.

Note: Fireplace model in illustrations may not be representative of your appliance.

Above

Snow

Level

Ground

Level

Figure 14 - Basement Installation

Basement

Wall

Inlet Grill in

8'max. Soffit (Overhang)

Figure 15 - Concrete Slab Installation

(Optional Outside Air Runs)

Duct Extended

to Miss Joist

To Outside Wall

Inside Wall

Outside Figure 14 - Basement Installation

Wall

Figure 16 - Installation Above Basement or

Figure 17 - 45° Corner Installation on

Crawl Space

Slab Floor

 

 

16

61D1013

Page 16
Image 16
Monessen Hearth BUF500, BUF400 for use of optional ak-4outside air kit, Basement Installation, Concrete Slab Installation