Monessen Hearth BUF400, BUF500 manual for use of optional ak-4outside air kit, located. See Figure

Models: BUF400 BUF500

1 20
Download 20 pages 43.44 Kb
Page 17
Image 17
Figure 18 - Attaching Outside Air Starting Collar

for use of optional ak-4 outside air kit

The use of outside air for combustion is optional unless required by building codes. It is only necessary to supply outside combustion air to one side of the fireplace. Use the model AK4 combustion air kit.

Model AK-4 Combustion Air Assembly

1.Remove the cover plate from the 4" outlet opening location on the left or right outside of the fireplace.

2.Place the insulation ring between the AK-4 starting collar and fire- place wall.

WARNING

DO NOT remove the cover if the outside air will not be connected.

3.Place the starting collar (4") into the hole on the side of fireplace. Fasten it in place with the four sheet metal screws provided. See Figures 18 and 19.

Note: The air starting collar extends through the fireplace outer wrap. When the air starting collar is securely attached, it will form a seal against the fireplace wall.

4. Attach outside duct to starting collar with duct clamp or screws. See Figure 19.

 

Left Side of

Insulation Ring

 

 

 

 

 

Fireplace

 

Screws

 

Air Starting

 

 

AK-4 Starting

 

 

 

 

 

 

 

 

Collar

 

 

 

Collar

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duct

 

 

 

Sheet

 

 

 

 

 

 

 

Meal

 

 

 

 

 

 

 

Screws

 

 

 

 

 

 

Shorter End

 

 

 

Left Side of

 

 

 

 

 

 

Fireplace

 

 

 

of Air Starting

 

 

 

 

 

 

 

Collar

 

 

Figure 19 - Attaching Outside Duct

Figure 18 - Attaching Outside Air Starting Collar

 

 

to Starting Collar

 

 

 

 

 

 

and Insulation Ring to Left Side of Fireplace

 

6" Diameter

 

 

 

 

 

 

 

 

 

5. Cut a 6-inch diameter opening for model AK-4 in the

Hole

 

Screw

 

 

 

outside wall covering where the outside vent is to be

 

 

 

 

located. See Figure 20.

 

 

 

 

Nail

6. Select and cut a piece of duct long enough to attach

 

 

 

 

Holes

 

to the fireplace and stick out at least 3" beyond the

 

 

 

 

 

 

 

face of the wall to which the AK-4 inlet air vent will be

Duct

 

 

 

attached. See Figure 19.

 

Extending

 

 

 

 

 

 

 

 

WARNING

 

 

 

 

3"min.

 

 

Use FP-4 U duct for maximum efficiency

 

 

AK-4 Inlet

 

 

and safety. Do not use a combustible

 

 

Air Vent

Screws

 

duct. Always use UL Listed Class 0 or

 

 

 

 

 

 

 

 

 

1 duct material.

 

 

Figure 20 - Combustion Air Assembly for

 

 

 

 

 

 

Model No. AK-4

 

 

 

 

 

 

 

 

Continued

61D1013

17