Monessen Hearth CWC400 CWC Series Woodburning Fireplace, Installing Outside Air Kit, 87D1504

Models: CWC500 CWC400

1 24
Download 24 pages 14.44 Kb
Page 11
Image 11
Installing Outside Air Kit

Installing Outside Air Kit

An outside air kit is installed in all CWC Series Fire- places. If desired, or if local codes mandate the use of an air kit, then an AK-MST is required to complete the installation (from air kit to the outdoors). If the outside air kit is to be used, the AK-MST MUST be installed BEFORE the fireplace is enclosed. Refer to the AK- MST instructions for field installation. The outside air control lever is located at the front edge of the left side brick. To ‘open’, push the control lever down toward the hearth brick. To ‘close’, pull the control lever up and over. (Fig. 16)

CWC Series Woodburning Fireplace

Inner Pipe Section

Pipe

Rim

UP

Elbow Strap Hem

Lance

Pipe

Rim

FPC558

Fig. 17 Install pipe, listening for the snap-lock to fasten.

Elbow Strap

Angled Strap

FP270/271

Support Structure

Elbow Strap (Must be tight)

Ceiling

Hole

Framing

Installing the Chimney System Angle Firestop

Installing the Firestop Spacer Chimney Support Strap (Must be tight)

CLOSED

OPEN

FP710

Fig. 16 Outside air operation.

Installing the Chimney System

Start by attaching the first chimney section to the collar on top of the fireplace.

Install the pipe as pictured in Figure 17. When you get a good lock, you will hear the pipe clearly snap together. Once sections are snap-locked in place, it is extremely difficult to get them apart. Make sure the pipe is firmly snapped and locked together as each pipe section is mounted.

When installing elbows, only outer pipe will snap- lock. Middle pipes simply slide into position. Be sure to always attach straps on upper elbow to a structural framing member. (Fig. 18)

Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.

Installing the Firestop Spacer

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly and required for safety.

Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.

Fig. 18 Attach straps to a structural framing member.

Hole sizes listed in Figure 13 for angled firestop spacers provide minimum required air space to chimney pipe for ceiling thickness up to 8" (203 mm). When combined thickness of ceiling material, ceiling joists and flooring material exceeds 8" (203 mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.

Proper Firestop Spacer Installation

Figure 19 shows different installation procedures for both an area that is an attic and an area that is not an attic.

If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole.

If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed

87D1504

11

Page 11
Image 11
Monessen Hearth CWC400, CWC500 CWC Series Woodburning Fireplace, Installing Outside Air Kit, Installing the Chimney System