CWC Series Woodburning Fireplace

Combustible

12"

 

Mantel and

 

(305mm)

Finished Wall

 

Trim

 

Max.

 

1Z\x"

Header

(38mm)

Standoff

12" (305mm)

Noncombustible

Min.

6"

Material

(159mm)

 

Min.

Grille

 

 

Opening

Top View

Fireplace

 

Opening

Z\x" 2 x 4 Stud

Finished Wall

Fireplace Front Must be sealed with non- combustible material

FP531b

Fig. 22 Mantel clearance.

used below a flat mantel shelf, consult your local building codes for minimum clearance from top of fireplace open- ing to bottom of mantel shelf.

All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 22 and 23)

NOTE: No side wall protection is required for fireplaces installed at 45° to two (2) side walls (corner installation).

Often a decorative surround or vertical portion of the mantel is desired. If this is constructed of any combus- tible material it must be within the safe zone indicated in Figure 23.

Side Wall Protection

Adjacent combustible side walls that are within the mini- mum dimensions shown in Figure 24 of fireplace open- ing must be protected with MHSC Wall Shield Model SP40 or a specifically built wall shield described below.

The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

1Z\x"

Ref.

*12" from top of grille opening for circu- lating models

**6" from top of grille opening for circu- lating models

Face Plate

*

**

Combustible materials are permitted within a shaded area shown in Figure 23 titled Minimum Wall Clearances.

MA81

Fig. 23 Combustible mantel clearances.

14

87D1504

Page 14
Image 14
Monessen Hearth CWC500, CWC400 manual Side Wall Protection, From top of grille opening for circu- lating models, Top View