CONNECTING THE GAS
NOTICE: A qualified gas appliance installer must connect the heater to the gas supply. Consult all local codes.
CAUTION
Use new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (Listed on Data Plate) at the maximum flow rate (BTU/Hr). Undue pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. Refer to Figure 15.
Pipe Coupling | Locations that the | |
Pressure Tapping | ||
To Heater | Point May Be | |
Valve | ||
Installed | ||
|
Stainless
Flexible Tube
Pipe
Gas Supply Inlet
Manual Shutoff
Valve
Figure 15 - Gas Connection
IMPORTANT: Hold heater valve firmly with a wrench to prevent movement when connecting to inlet pipe.
CAUTION
CHECK GAS TYPE: The gas supply must be the same as stated on the heater’s rating plate. If the gas supply is different, DO NOT INSTALL THE HEATER. Contact your dealer for the correct model.
Always use an external regulator for all propane/LPG heaters only, to reduce the supply tank pressure to a maximum of
13" w.c. This is in addition to the internal regulator in the heater valve.
14D2099 | 19 |