Thermostat control has three (3) positions:
OFF -All gas to the gas logs is shut off at the valve.
IGN -Valve position to light/maintain a standing pilot.
LOW/HI -Variable position corresponding to desired temperature. Both front and rear burners are in operation to
provide realistic glow and yellow flame.
Milli-Volt control has four (4) positions:
OFF -All gas to the gas logs is shut off at the valve.
IGN -Valve position to light/maintain a standing pilot.
ON -Valve position to turn ON/OFF log set with remote switch/thermostat or with ON/OFF switch on the set.
LOW/HI -Variable position to control flame height (heat output). Both front and rear burners are in operation to
provide realistic glow and yellow flame.
GENERAL INSTALLATION INFORMATION
CODES
Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 or
NFPA54 which can be obtained from…
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
or
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
ADEQUATE COMBUSTION AND VENTILATION AIR
This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for
adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1), defines a confined space as a space whose volume is less than 50 cubic feet
per 1,000 BTU per hour (4.8 m3per kw) of the aggregate input rating of all appliances installed in that space. An unconfined
space is defined as a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8 m3per kw) of the
aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the
appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
UNUSUALLY TIGHT CONSTRUCTION IS DEFINED AS CONSTRUCTION WHERE…
a) walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of 1 perm
(6 x 1011 kg per-pa-sec-m2) or less with openings gasketed or sealed, and
b) weather striping has been added on openable windows and doors, and
c) caulking or sealant are applied to areas such as joints around windows and door frames; between sole plates and doors;
between wall-ceiling joints; between wall panels; at penetrations for plumbing, electrical, and gas lines; and at other
openings.