CLEARANCES AND HEIGHT REQUIREMENTS

CLEARANCES AND HEIGHT REQUIREMENTS

Ensure that minimum clearances shown in Figures 4 through 7 are maintained. Left and right clearances are determined when facing the front of the firebox.

Follow these instructions carefully to ensure safe installation. Failure to follow these requirements may create a fire hazard.

1.Sidewall clearances: The clearance from the inside of the appliance to any combustible wall should not be less than 6". See Figure 4.

2.Ceiling clearance: The ceiling must be at least 42” from the top of the firebox opening. See Figure 4.

3.Back wall clearance: The appliance may be placed against a combustible back wall.

Minimum42"

6" Minimum

Min

6"

imum

 

Figure 4 - Clearance and Height

Requirements

4.Floor clearance: This inner chamber firebox floor must be installed at least 6" above any combustible flooring mate- rial, such as carpeting or asphalt tile, which is closer than 14" to the base of the firebox. See Figure 5.

Or

The inner chamber firebox floor may be installed nearer to the floor if a minimum of 14" of noncombustible material such as slate or marble is installed between the base of the firebox and the combustible flooring. See Figure 6.

 

Can Be

Non-Combustible

Combustible

Less than 6"

 

Material

Material

 

 

 

6" Minimum

14" Minimum

 

 

 

 

Figure 6 - Minimum Clearance above Combustible

Figure 5 - Minimum Clearance above

Flooring with Non-Combustible Material Installed at

Combustible Flooring

Base of Fireplace