Mr. Heater MHT 45 Typical Installation, Venting, Canadian Installations1, US Installations2

Models: MHT 45

1 24
Download 24 pages 51.43 Kb
Page 12
Image 12
Typical Installation

Typical Installation

 

 

Section 4 VENTING

The Illustration below shows a typical installation of the MHT tube

This appliance is certified under the ANS/CSA Standard for Vented

heater. The installation drawing shown has a straight horizontal

Gas-Fired Space Heating Appliances. In accordance with these

venting arrangement and specifies the minimum space required for

standards all sidewall venting must conform to the supplied diagram

maintenance, as well as the allowable range of distances between

for Vent Terminal Clearances, which are stated for both U.S. and

the two suspension points.

 

 

 

Canadian installations. These clearances should be compared

Detailed venting arrangements are illustrated in following portions of

to but not less than those specified in the current ANSI Z223.1/

NFPA 54, National Fuel Gas Code, or CSA B149.1, Natural Gas and

this section.

Minimum

 

 

 

 

Propane Installation Code. Clearances not covered in the table or

 

Recommended

 

6" Min

 

 

above listed codes must comply with local installation codes and the

 

for servicing

 

X

 

 

 

requirements of your local gas supplier.

24"

15"

1" Max.

Suspension

 

 

 

Points

 

Vent terminal

Burner Box

Reflector

 

 

 

 

 

 

Exterior Wall

 

 

 

 

Outside wall thickness -

 

 

 

10" max. 1/2" min.

 

Minimum Mounting

 

 

 

 

 

 

 

 

Height- 7 feet*

 

XDimension

Model Min. Max.

MHT-45 102" 114"

(*)For minimum mounting height in aircraft hangars and public garages.

 

 

 

 

Canadian Installations1

 

 

US Installations2

 

A=

Clearance above grade,

 

12 inches (30 cm)

 

 

12 inches (30 cm)

 

 

veranda, porch, deck or

 

 

 

 

 

 

 

balcony

 

 

 

 

 

 

B=

Clearance to window or door

 

6 inches (15 cm) for appliances <

 

 

6 inches (15 cm) for appliances <

 

 

that may be opened

 

10,000 Btuh (3 kW), 12 inches (30

 

 

10,000 Btuh (3 kW), 9 inches (23

 

 

 

 

cm) for appliances > 10,000 Btuh

 

 

cm) for appliances > 10,000 Btuh

 

 

 

 

(3 kW) and < 100,000 Btuh (30

 

 

(3 kW) and < 50,000 Btuh (15

 

 

 

 

kW), 36 inches (91 cm) for

 

 

kW), 12 inches (30 cm) for

 

 

 

 

appliances > 100,000 Btuh (30 kW)

 

 

appliances > 50,000 Btuh (15 kW)

 

C=

Clearance to permanently

 

*

 

 

*

 

 

closed window

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D=

Vertical clearance to ventilated

 

*

 

 

*

 

 

soffit located above the

 

 

 

 

 

 

 

terminal within a horizontal

 

 

 

 

 

 

 

distance of 2 feet (61 cm) from

 

 

 

 

 

 

 

the center line of the terminal

 

 

 

 

 

 

E=

Clearance to unventilated soffit

 

*

 

 

*

 

F=

Clearance to outside corner

 

*

 

 

*

 

G=

Clearance to inside corner

 

*

 

 

*

 

H=

Clearance to each side of

 

3 feet (91 cm) within a height 15

 

 

 

 

 

center line extended above

 

feet (4.5 m) above the

 

 

*

 

 

meter/regulator assembly

 

meter/regulator assembly

 

 

 

 

I=

Clearance to service regulator

 

3 feet (91 cm)

 

 

*

 

 

vent outlet

 

 

 

 

 

 

J=

Clearance to nonmechanical air

 

6 inches (15 cm) for appliances <

 

 

6 inches (15 cm) for appliances <

 

 

supply inlet to building or the

 

10,000 Btuh (3 kW), 12 inches (30

 

 

10,000 Btuh (3 kW), 9 inches (23 cm)

 

 

combustion air inlet to any

 

cm) for appliances > 10,000 Btuh (3

 

 

for appliances > 10,000 Btuh (3 kW)

 

 

other appliance

 

kW) and < 100,000 Btuh (30 kW),

 

 

and < 50,000 Btuh (15 kW), 12

 

 

 

 

36 inches (91 cm) for appliances

 

 

inches (30 cm) for appliances >

 

 

 

 

> 100,000 Btuh (30 kW)

 

 

50,000 Btuh (15 kW)

 

K=

Clearance to a mechanical air

 

6 feet (1.83 m)

 

 

3 feet (91 cm) above if within 10 feet

 

 

supply inlet

 

 

 

 

(3 m) horizontally

 

L=

Clearance above paved

 

7 feet (2.13 m) +

 

 

*

 

 

sidewalk or paved driveway

 

 

 

 

 

 

 

located on public property

 

 

 

 

 

 

M=

Clearance under veranda,

 

12 inches (30 cm) ++

 

 

*

 

 

 

 

 

porch deck, or balcony

 

 

 

 

 

 

1

In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.

 

 

2

In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.

 

 

+

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

 

++

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

 

 

*

For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be indicated:

 

 

 

a) A minimum clearance value determined by testing in accordance with section 2.19.6, or;

 

b) A reference to the following footnote:

“Clearance in accordance with local installation codes and the requirements of the gas supplier.”

Mr. Heater Gas-Fired Low-Intensity Infrared Heater 12 Operating Instructions and Owner’s Manual