Section 7 TROUBLESHOOTING

Section 7 TROUBLESHOOTING

General

This troubleshooting quide has been designed to assist you in locating and correcting minor problems that may occur with the MHT tube heater.

BLOWER DOES NOT COME ON

Possible Cause

 

Try This….

 

 

 

Power cord is not plugged in.

 

Plug power cord into a grounded three prong Outlet.

 

 

 

Thermostat setting is too low.

 

Increase thermostat temperature setting.

 

 

 

DSI module needs to be reset.

 

Unplug heater power cord from the electrical Outlet: wait for a

minimum of five seconds. Plug heater cord back

into outlet.

 

 

 

 

No power at electrical outlet.

 

Replace fuse or reset circuit breaker

 

 

 

Faulty blower motor

 

Replace blower motor.

 

 

 

IGNITER DOES NOT SPARK

Possible Cause

Try This…..

 

 

DSI module needs to be reset.

Unplug heater power cord from the electrical outlet: wait for a

 

minimum of five seconds. Plug heater cord back into outlet.

 

 

Faulty igniter or ignition wire.

Unplug heater power cord from the electrical outlet; check igniter and

ignition wire for damage. If damaged, replace igniter and/or ignition

 

 

cable.

 

 

Air switch does not operate.

Check flue/air supply duct for obstructions; remove obstructions as

 

required. Check for loose/leaky air hoses to the air switch; repair/

 

replace/tighten hoses as required. Check for 24V across the secondary

 

terminals 4 and 5 (red and yellow wires) of the transformer. IF NO:

 

Check for 120V across the primary terminals 1 and 3 (black and white

 

wires) of the transformer. If 120V is present, replace transformer. If 120V

 

is not present, check wiring between power cord, blower motor and

 

transformer. IF YES: Connect a jumper wire across air switch terminals;

 

if jumper wire allows blower to operate, replace pressure switch (see

 

replacement parts list for part number that applies to your unit rating).

 

 

Igniter spark gap incorrect.

Reset spark gap to 1/8’ (0.125”).

 

 

 