BURNER DOES NOT LIGHT
Possible Cause | Try This…. | |
Air in the gas line. | Purge gas lines. | |
|
| |
Improper gas inlet pressure. | Check gas inlet pressure at the 1/8” NPT plugged tap. Gas inlet | |
pressure should be as follows: | ||
| ||
| Natural Gas: 5.0”w.c. min.; 10.5” max. | |
| LP Gas: 11”w.c. min.; 13.0” max. | |
| If gas inlet pressure does not meet inlet pressure requirements | |
| contact the gas company. | |
|
| |
Gas valve does not open. | Check for 24V across valve terminals. | |
| Check Shutoff On Valve. | |
| IF NO: Check wiring between the ignition module and the valve. | |
| Repair/replace wires as required. If wiring is OK, replace ignition | |
| module. IF YES: Replace gas valve. | |
|
| |
Low gas outlet pressure. | Check gas manifold pressure. Measure manifold pressure at the | |
| ||
| pressure tap on the gas valve. | |
| Check gas manifold pressure. Measure manifold pressure at the | |
| pressure tap on the gas valve. Natural Gas: 4.0” w.c. LP Gas: 10.0” | |
| w.c. If manifold pressure does not meet requirements, adjust valve | |
| outlet pressure with the adjustment screw on the valve. NOTE: | |
| Proper inlet gas pressure must be verified before performing outlet | |
| pressure testing. |
BURNER DOES NOT STAY LIT
Possible Cause | Try this….. |
Damaged wires between DSI module and electrode. | Replace wires as required. |
|
|
Faulty DSI module | Replace DSI module. |
|
|
Damaged Electrode | Replace Electrode |
|
|