DCA-36SPX — OUTPUT TERMINAL PANEL FAMILIARIZATION

Output Terminal Panel

The OutputTerminal Panel (Figure 8) shown below is located on the right-hand side (left from control panel) of the generator. Lift up on the cover to gain access to receptacles and terminal lugs.

Output Terminal Familiarization

The “OutputTerminal Panel ” (Figure 8) is provided with the following:

Two 120/240V output receptacles (CS-6369), 50A

Two auxilliary circuit breakers, (for CS-6369), 50A

Two 120V GFCI receptacles @ 20 amp

Two GFCI circuit breakers @ 20 amps

Four Output Terminal Lugs ( U, O, V and Ground)

SINGLE PHASE

 

240 -120 VAC

GROUND

OUTPUT TERMINALS

TERMINAL

U O V

HARD WIRE

HOOKUP PANEL

BLACK WHITE RED

GREEN

NEUTRAL

TERMINAL

CIRCUIT BREAKERS

CIRCUIT BREAKERS

FOR GFCI RECEPTACLES

FOR CS-6369 TWIST

LOCK RECEPTACLES

120 VAC, 20 AMP

GFCI RECEPTACLES

ACCESS DOOR

LIFT TO OPEN

RECEPTACLE

 

 

AND

 

 

CIRCUIT BREAKER

 

 

PANEL

 

Y

 

 

 

W

X

 

 

 

 

CS-6369

 

 

TWIST-LOCK

 

AUX. POWER RECEPTACLES

 

 

120/240V, 50 AMPS

 

Figure 8. Output Terminal Panel

PAGE 26 — DCA-36SPX— OPERATION AND PARTS MANUAL — REV. #1 (04/14/10)

Page 26
Image 26
Multiquip operation manual DCA-36SPX Output Terminal Panel Familiarization, Output Terminal Familiarization