DCA-400SSK — OUTPUTTERMINAL PANEL OVERVIEW

OUTPUT TERMINAL FAMILIARIZATION

The “Output Terminal Panel” is provided with the following:

zTwo 120V GFCI receptacles, 20 amp

zThree 120/240V output receptacles, 50 amp

zTwo 120V output receptacles, 20 amp (optional)

z3 Circuit Breakers 240V @50 amps

z2 GFCI Circuit Breakers 125V@ 20 amps

Control Box

The “Control Box” is provided with the following:

zMain Circuit Breaker 1000 amps

zOver-Current Relay

Output Terminal Panel

The Output Control Panel (See Figure 14) is located on the right hand side (left from control panel) of the generator. The UVWO lugs are protected by a face plate cover that can be secured in the close position by a pad lock. (See Figure 11).

FIGURE 11. Output Terminal Cover

120 Volt Recetacle

Two GFCI Duplex Nema 5-20R (120V, 20 Amp) recepacle is provided on the output terminal. This receptacle can be used anytime the generator is in operation. The receptacle is controlled by the circuit breaker located on the control panel.

Pressing the reset button resets the receptacle after being tripped. Pressing the "Test Button" (See Figure 12) in the center of this receptacle will check the GFCI function. The receptacle should be tested at least once a month.

FIGURE 12. GFCI Test Button

Connecting Load

Loads can be connected to the generator by the UVWO Lugs or the convenience receptacles. (See figure 13). Make sure to read the operation manual before attempting to connect a load to the generator.

FIGURE 13. Connecting Load

Circuit Breakers

To protect the generator from an overload, a 3-pole, 1000 amp, main circuit breaker is provided to protect the UVW output terminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload. Three 50 amp load circuit breakers have also been provided to protect the load side of the generator from overload. Make sure to switch ALL circuit breakers to the "OFF" position prior to starting the engine.

Maximum Output

The entire load connected to the UVWO Lugs, all four slots in the duplex receptacles, and the must not exceed 352 kW in standby or 320 in prime output.

Twist Lock Dual Voltage Receptacles

Three CS-6369 auxiliary power receptacles have been provided to supply 208/120V. The voltage regulator knob on the control panel may need to be used to adjust the voltage to 208 or 416V.

Input Receptacles

Two 120 volt, 20 amp input receptacles are provided to supply power to accessories, such as the battery charger (optional) or jacket water heater (optional).

PAGE 34 — DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01)

Page 34
Image 34
Multiquip operation manual DCA-400SSK Outputterminal Panel Overview

DCA-400SSK specifications

The Multiquip DCA-400SSK is a robust solution designed for a variety of construction and developmental applications. Known for its reliability and efficiency, this three-phase diesel generator is equipped with a powerful engine that offers dependable performance in the field.

One of the standout features of the DCA-400SSK is its 400 kW output capacity, making it an ideal choice for large-scale operations where consistent power supply is crucial. It is powered by a high-performance, durable diesel engine that meets stringent emissions standards, ensuring compliance while delivering high efficiency.

The DCA-400SSK comes equipped with advanced technology that enhances its usability and performance. Its automatic voltage regulation (AVR) system ensures stable voltage under varying load conditions, which is essential for sensitive electrical equipment. This feature provides peace of mind to operators, knowing that their equipment is protected from voltage fluctuations.

Built with a sound-attenuated enclosure, the DCA-400SSK is designed to minimize noise, making it suitable for operation in noise-sensitive environments. This aspect not only protects the hearing of those working nearby but also ensures compliance with local noise regulations, thereby promoting a safer working environment.

Another remarkable characteristic of the DCA-400SSK is its user-friendly control panel, which features easy-to-read gauges and straightforward controls. This makes monitoring and operating the generator simple, even for those with limited experience in generator operation. With remote start capabilities, users can start and stop the generator from a distance, enhancing efficiency and convenience.

In terms of mobility, the DCA-400SSK is designed with integrated lifting points and forklift pockets, which facilitate easy transport around job sites. Its rugged construction ensures durability, able to withstand the harsh conditions typical of construction sites while maintaining optimal performance.

Overall, the Multiquip DCA-400SSK stands as a reliable and efficient diesel generator, combining powerful output with advanced features and environmental considerations. It is tailored to meet the demands of contractors and operators looking for a versatile and sturdy power solution. Whether for temporary power needs or long-term projects, the DCA-400SSK delivers exceptional performance in a compact and user-friendly package.