Multiquip DCA-400SSK Before Starting Engine, Before Starting Generator and Control Panel

Models: DCA-400SSK

1 114
Download 114 pages 44.3 Kb
Page 47
Image 47

DCA-400SSK — GENERATOR START-UP PROCEDURE (MANUAL)

WARNING:

The engine's exhaust contains harmful emissions. ALWAYS ventilate the exhaust when operating inside tunnels, excavations or buildings. Direct exhaust away from nearby personnel.

Before Starting

Engine

1.Check the lubricating oil level prior to starting the engine. Make sure the generator is level. The oil level must be maintained between two notches on the dipstick.

2.When there is not enough lubricating oil, fill the crankcase with high grade motor oil. Use a high quality detergent oil classified CC or higher (See Table 11 on page 43).

3.Check the coolant level in the radiator and subtank. Replenish with antifreeze as necessary. Always maintain the coolant level between the FULL and LOW markings on the coolant container. Be sure the radiator cap is fastened securely.

4.Check the fuel level on the fuel gauge. If fuel is low, fill the fuel tank with clean fresh unleaded automotive diesel. If diesel spillage occurs, completely wipe up the spilled fuel immediately.

Before Starting

Generator and Control Panel

CAUTION:

NEVER start the engine with the main,

GFCI or load circuit breakers in the ON

position.

1.Be sure to disconnect the electrical load and switch the main, load and G.F.C.I. circuit breakers (Figure 31) to the “OFF” position prior to starting the engine.

Jacket Water Heater and Internal Battery Charger 120 VAC Output Receptacles (OPTIONAL)

This generator is equipped with two 120 VAC, 20 amp output receptacles located on the output terminal panel, page 43, Figure 14.

The purpose of these receptacles is to provide power via commercial power to the jacket water heater and internal battery charger.

These receptacles will ONLY function when commercial power has been supplied to them (Figure 31). To apply commercial power to these receptacles, a power cord of adequate size will be required.

When using the generator in hot climates there is no reason to apply power to jacket water heater. However, if the generator will be used in cold climates it is always a good idea to apply power to the jacket water heater at all times.To apply power to the jacket water heater simply apply power to the jacket water heater receptacle via commercial power using an power cord of adequate size.

If the generator will be used daily, the battery should normally not require charging. If the generator will be idle (not used) for long periods of time, apply power to the battery charger receptacle via commercial power using an power cord of adequate size.

When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator's internal battery charger. This will ensure that the engine will not fail due to a dead battery.

CAUTION:

ALWAYS have power applied to the generator's internal battery charger when connecting the generator to a isolation (transfer) switch. Remember before connecting this generator to any buildings electrical system, have a licensed electrician perform the installation of the transfer switch.

Figure 31. Main, GFCI and Load Circuit Breakers

DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01) — PAGE 47

Page 47
Image 47
Multiquip DCA-400SSK operation manual Before Starting Engine, Before Starting Generator and Control Panel