GENERATOR OUTPUTS/GAUGE READING

HOW TO READ THE AC AMMETER AND AC VOLTAGE GAUGES

The AC ammeter and AC voltmeter gauges are controlled by the AC ammeter and AC voltmeter change-over switches.

Both of these switches are located on the control panel and DO NOT effect the generator output. They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.

Jumper the voltage change-over board for 3Ø, 240V operation (Figure 13).

Figure 13. Voltage Change-Over Board 240V

Configuration.

AC Voltmeter Gauge Reading

Place the ACVoltmeter Change-Over Switch (See Figure 14) in the W-U position and observe the phase to phase voltage reading between the W and U terminals as indicated on the AC Voltmeter Gauge (Figure 15).

Figure 14. AC Voltmeter

Figure 15. AC Voltmeter

Change-Over Switch

Gauge

AC Ammeter Gauge Reading

Place the AC Ammeter Change-Over Switch (Figure 16) in the U position and observe the current reading (load drain) on the U terminal as indicated on the AC Ammeter Gauge (Figure 17). This process can be repeated for terminals V and W.

Figure 16. AC Ammeter

Figure 17. AC Ammeter

Change-Over Switch

(Amp Reading on U Lug)

NOTICE

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.