Multiquip dca25USI2 manual Connecting Loads, Over Current Relay

Models: dca25USI2

1 78
Download 78 pages 14.45 Kb
Page 22
Image 22

OUTPUT TERMINAL PANEL FAMILIARIZATION

Connecting Loads

Loads can be connected to the generator by the output terminal lugs or the convenience receptacles (Figure 11). Make sure to read the operation manual before attempting to connect a load to the generator.

To protect the output terminals from overload, a 3-pole, 60 amp main circuit breaker is provided. Make sure to switch ALL circuit breakers to the OFF position prior to starting the engine.

Over Current Relay

An over current relay (Figure 12) is connected to the main circuit breaker. In the event of an overload, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located in the control box.

Figure 12. Over Current Relay

Figure 11. Connecting Loads

page 22 — DCA25Usi2 60 hz Generator • operation and parts manual — rev. #0 (02/14/14)