Load Application

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

„„When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

„„When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

„„When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA25usi2 60 hz Generator • operation and parts manual — rev. #0 (02/04/14) — page 23

Page 23
Image 23
Multiquip dca25USI2 manual Load Application, Single Phase Load, Three Phase Load

dca25USI2 specifications

The Multiquip DCA25USI2 is a powerful and versatile portable generator designed for a range of applications in construction, events, and emergency power supply. This model is particularly noted for its durability and reliability, making it an excellent choice for both professionals and DIY enthusiasts.

At the heart of the DCA25USI2 is a robust 25 kW output, giving users plenty of power to run multiple tools, equipment, or systems simultaneously. This generator operates on a powerful water-cooled diesel engine, which not only enhances fuel efficiency but also extends the lifecycle of the machine compared to traditional gas-powered generators. The use of diesel fuel contributes to lower operational costs and makes it suitable for longer usage periods, particularly in remote locations.

One of the standout features of the DCA25USI2 is its compact design. Despite its high power output, this generator maintains a relatively small footprint, allowing for easy transportation and storage. Weighing around 1,800 pounds, it is fitted with a robust frame that provides durability while facilitating easy placement at job sites or outdoor events.

The generator is equipped with advanced noise reduction technology, ensuring that it operates quietly, which is crucial when working in residential areas or noise-sensitive environments. The sound-dampening enclosure significantly lowers operating noise levels, enhancing the overall user experience.

In terms of electrical output, the DCA25USI2 offers multiple options, including both single-phase and three-phase connections. This versatility allows users to power a variety of applications without needing additional adaptors. Moreover, the generator’s heavy-duty alternator ensures stable power delivery, protecting sensitive electronic devices from voltage spikes.

Another key characteristic of the DCA25USI2 is its user-friendly control panel, which features intuitive gauges and circuit breakers for easy management of power distribution. The panel includes a digital hour meter, allowing operators to track usage and plan for maintenance efficiently.

Safety features are also a priority with the DCA25USI2, including automatic shutdown capabilities to protect the engine against low oil levels and overheating. This thoughtful design helps to ensure both the performance and longevity of the generator.

In summary, the Multiquip DCA25USI2 stands out for its powerful output, efficient diesel engine, compact design, and advanced features, making it a top choice for anyone in need of reliable portable power. Whether for construction, events, or emergency backup, this generator is engineered to deliver exceptional performance and peace of mind.