GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by applying jumpers (6) to the voltage
Voltage Change-Over Board
The voltage
Figure 12. Voltage Change-Over Board
CAUTION
NEVER attempt to place jumper plates on the voltage
Table 7. Voltages Available
Three Phase | 208V | 220V | 240V | 416V | 440V | 480V | |
(Switchable) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
Single Phase | 120V | 127V | 139V | 240V | 254V | 277V | |
(Switchable) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
Generator Amperage
Tables 8 and 9 describe the generator’s current output capability for both
Table 8. Generator Ampere Ratings — 1Ø
kW | 120V | 139V | 240V | 277V | 480V |
80 | 222 | 191 | 111 | 96 | 55 |
110 | 305 | 263 | 152 | 131 | 76 |
140 | 388 | 335 | 194 | 167 | 97 |
170 | 472 | 407 | 236 | 203 | 118 |
200 | 555 | 480 | 277 | 240 | 138 |
230 | 638 | 551 | 319 | 275 | 160 |
260 | 722 | 623 | 361 | 311 | 180 |
290 | 805 | 695 | 402 | 347 | 201 |
320 (Max) | 889 | 767 | 444 | 383 | 222 |
These calculations refl ect the maximum amount of current the generator can provide at each output terminal pair. To obtain the total generator amperage, multiply by 3.
Example 1: 488.6 amps @ 120V per output terminal pair X 3 = 1,486 amps
Example 2: 244.3 amps @ 240V per out put terminal pair X 3 = 733 amps
Table 9. Generator Ampere Ratings — 3Ø
KVA | 240V | 480V |
100 | 240 | 120 |
130 | 312 | 156 |
160 | 384 | 192 |
190 | 457 | 228 |
220 | 529 | 264 |
250 | 601 | 300 |
280 | 674 | 337 |
310 | 746 | 373 |
340 | 818 | 409 |
370 | 890 | 445 |
400 | 962 | 481 |
PAGE 26 — DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08)