Multiquip SG1400C3 Before Starting, ALWAYS have adequate ventilation when operating, On Up

Models: SG1400C3

1 62
Download 62 pages 40.87 Kb
Page 34
Image 34
Before Starting
startup
FUEL VALVES IN PRIME MODE
Figure 21. Fuel Valves (Prime Mode) ON (UP)
Figure 22. Fuel Priming Switch (ON)
4. After priming is complete, release the fuel priming switch. Place the fuel valves in the run mode (Figure
23). FUEL VALVES IN
RUN MODE
Figure 23. Fuel Valves (Run Mode)
5. Verify that all three circuit breakers (Figure 24)are in the ON position prior to starting the engine.

Before Starting

ALWAYS have adequate ventilation when operating. CAUTION

The engine’s exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating.

1.Place the Control Power switch (Figure 18) on the digital control panel in the up position (ON).

ON (UP)

Figure 18. Control Power Switch (ON)

2.Place the voltage selector switch (Figure 19) in the desired voltage setting position. The corresponding Voltage Status LED on the control panel will light to indicate the selected voltage (Figure 20).

120/208 3ON (UP)

277/480 3Figure 18. Control Power Switch (ON)

120/240 1120/240 1
Figure 19. Voltage Selector Switch

120/208 3Ø Position

LIGHTS IFFigure 19. Voltage Selector Switch

SELECTED

Figure 20. Voltage Status LEDs

3.If it is necessary to prime engine before starting (such as after changing fuel filter or running out of fuel), place the fuel valves in the prime position (Figure 21). Place the fuel priming switch (Figure 22) in the up position.

VERIFY CIRCUIT

ON

 

 

 

 

BREAKERS ARE ON

 

 

 

Electronic Trip Unit

 

 

Test

Push to Trip

A — 500

E — 1250

 

450 AMP

B — 600

F — 1500

 

C — 800

G — 2000

 

LONG — INST.

D — 1000

H — 2500

Status

Figure 24. Circuit Breakers (ON)

page 34 — SG1400C3 Studio Generator • operation manual — rev. #0 (10/05/11)

Page 34
Image 34