PIPING

Standard Munchkin boiler

Retrofit piping (zoning with valves) Space heating mode

Drawing 1A

 

zone valves

 

make-up water

P1

 

 

 

 

 

flow

purging

 

bypass

valves

 

valve

 

 

V1

 

 

OFF

 

 

anti-scald

 

 

mixing valve

 

 

cold

 

 

water

 

T/P

 

 

Munchkin boiler

Super Stor

 

indirect DHW tank

 

 

NOTES:

 

 

1.This drawing is meant to show system piping concept only.

Installer is responsible for all equipment & detailing required by local codes.

2.Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode: Munchkin model 399M: 16 gpm

3.The minimum pipe size for connecting a Super Stor water heater is 1 inch.

4.The minimum pipe size for connecting a Munchkin boiler is 1.25 inches.

5.All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.

6.The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

7.Install a minimum of 12 diameters of straight pipe upstream of all circulators.

8.A purging valve may be used .in lieu of the ball valve / hose bib combination shown